Adjustment Level Section 5-4<br />

soak Soak Time<br />

Function<br />

Setting<br />

See<br />

wt-b Wait Band<br />

Function<br />

Setting<br />

See<br />

This parameter sets the time for the control operation when using the simple<br />

program function.<br />

The set value is saved in the Soak Time parameter for the current bank.<br />

Setting range Unit Default<br />

1 to 9999 min or h 1<br />

■ Related Parameters<br />

The Program Pattern parameter<br />

must not be set to OFF.<br />

Program start, Soak time remain (operation level): Page 184<br />

Bank * wait band, Bank * soak time (Bank setting level): Page 215<br />

Program pattern (initial setting level): Page 229<br />

Soak time unit (advanced function setting level): Page 266<br />

The Program Pattern parameter<br />

must not be set to OFF.<br />

This parameter sets the stable band within which the soak time is measured<br />

for the simple program function.<br />

The set value is saved in the Soak Time parameter for the current bank.<br />

Model Setting range Unit Default<br />

Temperature input OFF or 0.1 to<br />

3240.0<br />

°C or °F off<br />

Analog Input OFF or 0.01 to<br />

99.99<br />

%FS<br />

■ Related Parameters<br />

Program start, Soak time remain (operation level): Page 184<br />

Bank * wait band, Bank * soak time (Bank setting level): Page 215<br />

Program pattern (initial setting level): Page 229<br />

Soak time unit (advanced function setting level): Page 266<br />