Executing Heating/Cooling Control Section 4-4<br />

94<br />

When heating/cooling control is selected, the Dead Band and Cooling<br />

Coefficient parameters can be used.<br />

Dead Band For heating/cooling control, the dead band is set with the set point as its<br />

center. The dead band width is the set value of the Dead Band parameter<br />

(adjustment level). Setting a negative value produces an overlapping<br />

band.<br />

Output<br />

Heating<br />

side<br />

0<br />

Set point<br />

If an overlapping band is set, the bumpless function may not operate<br />

when switching between manual operation and automatic operation.<br />

The default is 0.0 EU for a temperature input and 0.00% FS for an analog<br />

input.<br />

Dead band: Dead band<br />

width = A positive value Output<br />

Cooling<br />

side<br />

PV<br />

Heating<br />

side<br />

0<br />

Set point<br />

Overlapping dead band: Dead<br />

band width = A negative value<br />

Cooling<br />

side<br />

Cooling Coefficient If the heating characteristics and cooling characteristics of the control object<br />

are very different and good control characteristics cannot be achieved with the<br />

same PID constants, the cooling coefficient can be used to adjust the proportional<br />

band (P) for the control output assigned to the cooling side. Use this to<br />

achieve balanced control between the heating side and cooling side. The proportional<br />

bands (P) for the control outputs assigned to the heating/cooling<br />

sides can be calculated using the following equations.<br />

P for control output assigned to heating side = P<br />

P for control output assigned to cooling side = P for control output assigned to<br />

heating side × cooling coefficient<br />

The cooling coefficient is multiplied by the P for the control output assigned to<br />

the heating side to obtain control with characteristics that differ from those of<br />

the control output assigned to the heating side.<br />

A cooling coefficient can be set for each PID set. To set the cooling coefficient,<br />

select the PID set number in the Display PID Selection parameter (PID setting<br />

level) and then set the Cooling Coefficient parameter. If the Cooling Coefficient<br />

parameter setting is changed in the adjustment level, the change will be<br />

reflected in the Cooling Coefficient parameter for the current PID set.<br />

Output Output<br />

P for control output<br />

assigned to heating<br />

side × 1.0<br />

P for control output<br />

assigned to heating<br />

side × 1.0<br />

P for control output<br />

assigned to heating side<br />

P for control output<br />

assigned to cooling side<br />

P for control output<br />

assigned to heating side<br />

P for control output<br />

assigned to cooling side<br />

0<br />

Set point<br />

PV<br />

0<br />

PV<br />

P for control output assigned to<br />

P for control output assigned to<br />

heating side × 0.8<br />

heating side × 1.5<br />

PV