Alarm Outputs Section 3-9<br />

PV Change Rate Alarm The change width can be found for PV input values in any set period. Differences<br />

with previous values in each set period are calculated, and an alarm is<br />

output if the result exceeds the alarm value. The PV rate of change calculation<br />

period can be set in units of 60 ms.<br />

If a positive value is set for the alarm value, the PV will operate as a change<br />

rate alarm in the rising direction. If a negative value is set, the PV will operate<br />

as a change rate alarm in the falling direction.<br />

SP Alarms When Remote<br />

SP Is Used<br />

70<br />

C<br />

Bank 1<br />

1.a-1 Alarm Value 1<br />

0.0<br />

C<br />

1.a-1<br />

10.0<br />

6. Press the M Key to select the Bank 1 Alarm Value 1 parameter.<br />

7. Use the U Key to set 10.0.<br />

Precaution<br />

If a shorter PV rate of change calculation period is set, outputs set for the PV<br />

change rate alarm function may repeatedly turn ON and OFF for a short<br />

period of time. It is therefore recommended that the PV change rate alarm be<br />

used with the alarm latch turned ON.<br />

Alarm value<br />

0<br />

Alarm function<br />

PV<br />

OFF<br />

Parameter name Setting range Unit Default<br />

PV Rate of Change<br />

Calculation Period<br />

ON<br />

OFF<br />

Time<br />

PV change width for PV rate<br />

of change calculation period<br />

1 to 999 Sampling cycle 17<br />

(= 17 × 60 ms = 1,020 ms)<br />

RSP Absolute Upper Limit and RSP Absolute Lower Limit parameters were<br />

added for the <strong>E5AN</strong>-H and <strong>E5EN</strong>-H (with remote SP input). These parameters<br />

are used for a remote SP regardless of whether the SP mode is set to<br />

Remote SP or Local SP Mode.<br />