Using a Remote SP Section 4-23<br />

SP Mode<br />

Remote SP Monitor<br />

SP Tracking<br />

156<br />

When the SP Upper Limit or SP Lower Limit parameter setting is<br />

changed, the remote SP upper or lower limit will be forcibly changed to<br />

the SP upper or lower limit. For example, if the upper limit for the SP limiter<br />

is changed from A to B, the remote SP upper and lower limits will be<br />

changed as shown in the following diagram.<br />

Before change<br />

After limiter upper limit change<br />

SP limiter<br />

RSP scaling range<br />

SP upper and lower limits<br />

Remote SP upper and lower limits<br />

Upper limit changed<br />

from A to B<br />

The SP mode is used to switch between local SP and remote SP. When a<br />

remote SP is selected in SP mode, the RSP single indicator will light.<br />

In remote SP mode, the remote SP can be checked on the No. 2 display in the<br />

PV/SP Display Screen. In local SP mode, it can be checked with the Remote<br />

SP Monitor parameter.<br />

If the SP tracking function is enabled, the local SP inherits the remote SP<br />

value after switching from remote SP to local SP. To enable the SP tracking<br />

function, set the SP Tracking parameter to ON.<br />

SP tracking operates as follows:<br />

LSP1<br />

LSP2<br />

RSP2<br />

SP mode<br />

LSP<br />

RSP LSP<br />

1,2,3... 1. Switching to remote SP when the SP is LSP1 will result in switching to<br />

RSP2.<br />

2. The operation will proceed according to remote SP inputs.<br />

3. If the SP tracking function is enabled, the SP will become LSP2 after<br />

switching to local SP. If the SP tracking function is disabled, the SP will remain<br />

as LSP1.<br />

If the SP tracking function is enabled when switching from local SP to<br />

remote SP, the SP ramp will operate.<br />

B<br />

A