Loop Burnout Alarm Section 4-12<br />

Initial Setting Level 3. Press the U Key to set the parameter to 12.<br />

To return to the operation level, press the O Key for at least one second.<br />

C<br />

PV/SP<br />

Operation Level 4. Press the O Key to move from the operation level to the PID setting level.<br />

Display PID<br />

PID Setting LevelSelection 5. The current PID set number will be displayed. Press the U or D Key to<br />

select PID set 2.<br />

118<br />

alt1 12<br />

25.0<br />

100.0<br />

d.pid 2<br />

2.lba 0<br />

2.lba 10<br />

in-t 5<br />

PID 2 LBA<br />

Detection Time<br />

6. Press the M Key to select the PID 2 LBA Detection Time parameter.<br />

7. Press the U Key to set the parameter to 10.<br />

Input Type<br />

Initial Setting Level 8. Press the O Key for at least three seconds to move to the initial setting<br />

level.<br />

amov 0<br />

init<br />

off<br />

Move to Advanced<br />

Function<br />

Setting Level<br />

9. Select the Move to Advanced Function Setting Level parameter by pressing<br />

the M Key. (For details on moving between levels, refer to 4-8 Moving<br />

to the Advanced Function Setting Level.)<br />

Parameter<br />

Advanced Function Initialization Setting Level 10. Press the D Key to enter the password (−169), and move from the initial<br />

setting level to the advanced function setting level.<br />

lbal<br />

8.0<br />

C<br />

LBA Level<br />

Advanced Function Setting Level 11. Select the LBA Level parameter by pressing the M Key.<br />

C<br />

lbal<br />

8.0<br />

lbab<br />

3.0<br />

12. Press the U Key to set the parameter to 8.0. (The default is 8.0.)<br />

C<br />

LBA Band<br />

Advanced Function Setting Level 13. Select the LBA Band parameter by pressing the M Key.<br />

C<br />

lbab<br />

3.0<br />

14. Press the U or D Key to set the parameter to 3.0. (The default is 3.0.)