Determining PID Constants (AT, ST, <strong>Manual</strong> Setup) Section 3-8<br />

ST Stable Range<br />

Operating Procedure The ST stable range determines the condition under which ST (self-tuning)<br />

functions.<br />

This procedure sets the ST stable range to 20°C.<br />

Advanced Function Setting Level 1. Select the ST Stable Range parameter by pressing the M Key in the ad-<br />

ST Stable<br />

Range<br />

vanced function setting level.<br />

3-8-3 RT (Robust Tuning)<br />

64<br />

C<br />

st-b<br />

1%0<br />

C<br />

st-b<br />

2*0<br />

rt<br />

2. Use the U Key to set the parameter to 20°C.<br />

When AT or ST is executed with RT selected, PID constants are automatically<br />

set that make it hard for control performance to degenerate even<br />

when the characteristics of the controlled object are changed.<br />

RT can be set in the advanced function setting level when PID control has<br />

been set.<br />

The RT mode cannot be selected while an analog input is set.<br />

Selecting the RT mode in the following cases will help to prevent hunting<br />

from occurring.<br />

When the set temperature is not constant and is changed in a wide<br />

range<br />

When there are large variations in ambient temperatures due to factors<br />

such as seasonal changes or differences between day and night temperatures<br />

When there are large variations in ambient wind conditions and air flow<br />

When heater characteristics change depending on the temperature<br />

When an actuator with disproportional I/O, such as a phase-controltype<br />

power regulator, is used<br />

When a rapidly heating heater is used<br />

When the control object or sensor has much loss time<br />

When hunting occurs in normal mode for any reason<br />

PID constants are initialized to the factory settings by switching to RT<br />

mode.<br />

When the RT mode is selected, the derivative time setting unit becomes<br />

the second.<br />

RT Features Even when hunting occurs for PID constants when AT or ST is executed<br />

in normal mode, it is less likely to occur when AT or ST is executed in RT<br />

mode.