Advanced Function Setting Level Section 5-10<br />

lbab LBA Band<br />

Function<br />

Setting<br />

See<br />

260<br />

Alarm 1 must be assigned.<br />

The alarm type must be set to 12<br />

(LBA).<br />

The LBA detection time must not be<br />

0. (See note.)<br />

This parameter sets the LBA band.<br />

If a control deviation greater than the LBA band is not reduced when the<br />

LBA level is exceeded, an loop burnout is detected.<br />

Note For ON/OFF control, the LBA Detection Time parameter (advanced<br />

function setting level) must not be set to 0. For 2-PID control, the<br />

LBA Detection Time parameter must not be set to 0 for any of PID<br />

sets 1 to 8.<br />

Models Setting range Unit Default<br />

Temperature input 0.0 to 3240.0 °C or °F 3.0<br />

Analog input 0.00 to 99.99 %FS 0.20<br />

■ Related Parameters<br />

Process value/Set point (operation level): Page 177<br />

Alarm 1 type (initial setting level): Page 231<br />

LBA detection time, LBA level (advanced function setting level): Page 259