Initial Setting Level Section 5-9<br />

Setting<br />

Set one of the set values from the following table.<br />

The default is 5.<br />

If a platinum resistance thermometer is mistakenly connected while a setting<br />

for other than a platinum resistance thermometer is in effect, S.ERR<br />

will be displayed. To clear the S.ERR display, check the wiring and then<br />

cycle the power.<br />

Input type Specifications Set value Input temperature range<br />

Platinum resistance Pt100 0 −200.0 to 850.0 (°C)/−300.0 to 1,500.0 (°F)<br />

thermometer<br />

1 −199.9 to 500.0 (°C)/−199.9 to 900.0 (°F)<br />

2 0.0 to 100.0 (°C)/0.0 to 210.0 (°F)<br />

JPt100 3 −199.9 to 500.0 (°C)/−199.9 to 900.0 (°F)<br />

4 0.0 to 100.0 (°C)/0.0 to 210.0 (°F)<br />

Thermocouple K 5 −200.0 to 1,300.0 (°C)/−300.0 to 2,300.0 (°F)<br />

6 −20.0 to 500.0 (°C)/0.0 to 900.0 (°F)<br />

J 7 −100.0 to 850.0 (°C)/−100.0 to 1,500.0 (°F)<br />

8 −20.0 to 400.0 (°C)/0.0 to 750.0 (°F)<br />

T 9 −200.0 to 400.0 (°C)/−300.0 to 700.0 (°F)<br />

10 −199.9 to 400.0 (°C)/−199.9 to 700.0 (°F)<br />

E 11 −200.0 to 600.0 (°C)/−300.0 to 1,100.0 (°F)<br />

L 12 −100.0 to 850.0 (°C)/−100.0 to 1,500.0 (°F)<br />

U 13 −200.0 to 400.0 (°C)/−300.0 to 700.0 (°F)<br />

14 −199.9 to 400.0 (°C)/−199.9 to 700.0 (°F)<br />

N 15 −200.0 to 1,300.0 (°C)/−300.0 to 2,300.0 (°F)<br />

R 16 0.0 to 1,700.0 (°C)/0.0 to 3,000.0 (°F)<br />

S 17 0.0 to 1,700.0 (°C)/0.0 to 3,000.0 (°F)<br />

B 18 100.0 to 1,800.0 (°C)/300.0 to 3,200.0 (°F)<br />

W 19 0.0 to 2,300.0 (°C)/0.0 to 3,200.0 (°F)<br />

PLII 20 0.0 to 1,300.0 (°C)/0.0 to 2,300.0 (°F)<br />

K 21 −50.0 to 200.0 (°C)/−50.0 to 200.0 (°F)<br />

J 22 −50.0 to 200.0 (°C)/−50.0 to 200.0 (°F)<br />

T 23 −50.0 to 200.0 (°C)/−50.0 to 200.0 (°F)<br />

Platinum resistance<br />

thermometer<br />

Pt100 24 −50.0 to 200.0 (°C)/−50.0 to 200.0 (°F)<br />

Current input 4 to 20 mA 25 One of the following ranges depending on the scal-<br />

Voltage input<br />

0 to 20 mA<br />

1 to 5 V<br />

26<br />

27<br />

ing.<br />

−19999 to 32400<br />

−1999.9 to 3240.0<br />

0 to 5 V 28 −199.99 to 324.00<br />

0 to 10 V 29<br />

−19.999 to 32.400<br />

See<br />

■ Related Parameters<br />

Temperature unit, Set point upper limit, Set point lower limit (initial setting<br />

level): Page 226<br />

225