PID Setting Level Section 5-6<br />

*.csc<br />

Function<br />

Setting<br />

See<br />

*.lba<br />

Function<br />

Setting<br />

See<br />

PID * Cooling Coefficient<br />

(*: 1 to 8)<br />

If the heating and cooling characteristics of the control object are very different<br />

and good control characteristics cannot be achieved with the same PID<br />

constants, the cooling coefficient can be used to adjust the proportional band<br />

(P) for the control output assigned to the cooling side. One parameter is set<br />

for each PID set.<br />

In heating/cooling control, the proportional band P for the cooling control<br />

output is calculated using the following formula to set the cooling coefficient:<br />

Cooling control output side P = Cooling coefficient × P (proportional band)<br />

The cooling coefficient will be set automatically if autotuning is executed<br />

when the Automatic Cooling Coefficient Adjustment parameter is set to<br />

ON. The execution results will be saved in the PID set where autotuning<br />

was started. If non-linearity is strong in the cooling characteristics, however,<br />

this function may not find the optimum cooling coefficient.<br />

Setting range Unit Default<br />

0.01 to 99.99 None 1.00<br />

■ Related Parameters<br />

PID (*) proportional band (PID setting level): Page 217<br />

PID * LBA Detection Time<br />

(*: 1 to 8)<br />

These parameters set whether the LBA function is to be enabled or disabled<br />

and sets the time interval for detection, for each PID set.<br />

These parameters set the time interval for detecting the LBA.<br />

Setting 0 disables the LBA function.<br />

For ON/OFF control, make the setting in the LBA Detection Time parameter<br />

in the advanced function setting level.<br />

Setting range Unit Default<br />

0 to 9999 s 0<br />

■ Related Parameters<br />

Alarm 1 type (initial setting level): Page 231<br />

LBA level (advanced function setting level): Page 259<br />

LBA band (advanced function setting level): Page 260<br />

Heating and cooling control and 2-<br />

PID control must be used.<br />

2-PID control must be used.<br />

Alarm 1 must be assigned.<br />

The alarm 1 type must be 12 (LBA).<br />