Appendix<br />

Action<br />

Control continues, allowing normal operation. The message is displayed when the PV, PV/SP, or PV/MV is displayed.<br />

Resistance thermometer input (Except for models with a<br />

setting range of −199.9 to 500.0°C)<br />

Thermocouple input (Except for models with a setting range of<br />

−199.9 to 400.0°C)<br />

Control range<br />

s.err display Numeric display s.err display<br />

Input indication range<br />

Analog Input<br />

• When display range < control range<br />

Control range<br />

s.err display [[[[ display Numeric display<br />

Input indication range<br />

e333<br />

Meaning<br />

There is an error in internal circuits.<br />

Action<br />

First, turn the power OFF then back ON again. If the display remains the same, the Controller must be<br />

repaired. If the display is restored, then the probable cause is electrical noise affecting the control system.<br />

Check for electrical noise.<br />

Operation<br />

Control output and alarm output turn OFF.<br />

e111<br />

Meaning<br />

Internal memory operation is in error.<br />

]]]] display s.err display<br />

−19999 Display range 32400 −19999 Display range 32400<br />

(See note.)<br />

(See note.)<br />

Action<br />

First, turn the power OFF then back ON again. If the display remains the same, the Controller must be<br />

repaired. If the display is restored, then the probable cause is electrical noise affecting the control system.<br />

Check for electrical noise.<br />

Operation at Error<br />

Control output and alarm output turn OFF. (Current output is approx. 0 mA).<br />

ffff<br />

AD Converter Error<br />

Memory Error<br />

Current Value Exceeds<br />

Meaning<br />

This error is displayed when the heater current value exceeds 55.0 A.<br />

Resistance thermometer input (Except for models with a<br />

setting range of −1999. to 500.0°C)<br />

Thermocouple input (Except for models with a setting range of<br />

−199.9 to 400.0°C)<br />

Control range<br />

s.err display [[[[ display Numeric display<br />

Input indication range<br />

s.err display<br />

Analog Input<br />

• When display range > control range<br />

Control range<br />

s.err display Numeric display s.err display<br />

Note: The display range is shown in numbers with decimal points omitted.<br />

305