312<br />

Appendix<br />

(2) Unless the Program Pattern parameter is set to OFF, the bank number will be from 0 to the value<br />

set for the Valid Program Bank parameter.<br />

Adjustment Level<br />

Parameters Characters Setting (monitor) value Display Default Unit Set value<br />

Adjustment Level<br />

Display<br />

l.adj<br />

AT Execute/Cancel at OFF: AT Cancel<br />

off, OFF None<br />

AT-2: 100%AT Execute at-2,<br />

AT-1: 40%AT Execute (See<br />

note 3.)<br />

at-1<br />

Communications<br />

Writing<br />

cmwt OFF, ON off, on OFF None<br />

Infrared Communications<br />

Use<br />

irdr OFF, ON off, on OFF None<br />

SP Mode spmd LSP, RSP lsp, rsp LSP None<br />

Heater Current 1<br />

Value Monitor<br />

ct1 0.0 to 55.0 A<br />

Heater Burnout<br />

Detection 1<br />

hb1 0.0 to 50.0 0.0 A<br />

Heater Overcurrent<br />

Detection 1<br />

oc1 0.0 to 50.0 50.0 A<br />

Heater Current 2<br />

Value Monitor<br />

ct2 0.0 to 55.0 A<br />

Heater Burnout<br />

Detection 2<br />

hb2 0.0 to 50.0 0.0 A<br />

Heater Overcurrent<br />

Detection 2<br />

oc2 0.0 to 50.0 50.0 A<br />

Leakage Current 1<br />

Monitor<br />

lcr1 0.0 to 55.0 A<br />

HS Alarm 1 hs1 0.0 to 50.0 50.0 A<br />

Leakage Current 2<br />

Monitor<br />

lcr2 0.0 to 55.0 A<br />

HS Alarm 2 hs2 0.0 to 50.0 50.0 A<br />

Heater Burnout<br />

Detection 1<br />

hb1 0.0 to 50.0 0.0 A<br />

Heater Burnout<br />

Detection 2<br />

hb2 0.0 to 50.0 0.0 A<br />

SP 0 sp-0 SP lower limit to SP upper<br />

limit<br />

0 EU<br />

SP 1 sp-1 SP lower limit to SP upper<br />

limit<br />

0 EU<br />

SP 2 sp-2 SP lower limit to SP upper<br />

limit<br />

0 EU<br />

SP 3 sp-3 SP lower limit to SP upper<br />

limit<br />

0 EU<br />

Temperature Input<br />

Shift<br />

ins −199.99 to 32400 0.00 °C or °F<br />

Upper Limit Temperature<br />

Input Shift<br />

Value<br />

insh −199.99 to 32400 0.00 °C or °F<br />

Lower Limit Temperature<br />

Input Shift<br />

Value<br />

insl −199.99 to 32400 0.00 °C or °F