Using the Simple Program Function Section 4-16<br />

Program Pattern Any of three program patterns can be selected. The simple program will not<br />

be run if the Program Pattern parameter is set to OFF.<br />

Program Pattern Operation<br />

OFF Program will not be executed.<br />

STOP Program operation will start when the Program Start parameter<br />

is changed from RSET to STRT. The bank number will be<br />

automatically incremented by one when the Soak Time<br />

parameter setting for the bank has elapsed.<br />

After the bank specified in the Valid Program Bank parameter<br />

has been executed, program operation will be ended. The<br />

RUN/STOP status will become STOP, and the program end<br />

output will be turned ON.<br />

CONT Program operation will start when the Program Start parameter<br />

is changed from RSET to STRT. The bank number will be<br />

automatically incremented by one when the Soak Time<br />

parameter setting for the bank has elapsed.<br />

After the bank specified in the Valid Program Bank parameter<br />

has been executed, program operation will be ended. The<br />

RUN/STOP status will continue as RUN (control will continue<br />

at the SP at the end bank), and the program end output will<br />

be turned ON.<br />

LOOP Program operation will start when the Program Start parameter<br />

is changed from RSET to STRT. The bank number will be<br />

automatically incremented by one when the Soak Time<br />

parameter setting for the bank has elapsed.<br />

After the bank specified in the Valid Program Bank parameter<br />

has been executed, the bank number will return to 0 and<br />

the program execution will continue.<br />

Banks where the Soak Time parameter is set to 0 will not be executed.<br />

The bank number can be changed even during program operation by using either an<br />

event input or key operations.<br />

The bank number is initialized to 0 when the program pattern is changed.<br />

■ Pattern 1 (STOP)<br />

Control will stop and the STOP mode will be entered when the program has<br />

ended.<br />

Set point n<br />

SP<br />

PV<br />

Wait band<br />

Wait band<br />

Soak time<br />

END display<br />

END output<br />

Automatically switches from RUN to STOP mode.<br />

Bank n (end bank)<br />