340<br />

pmov<br />

0<br />

M<br />

oapt<br />

0<br />

M<br />

icpt<br />

0<br />

M<br />

wtpt<br />

off<br />

M<br />

Protect Level<br />

The time taken to move to the protect level<br />

can be adjusted by changing the "Move to<br />

protect level time" setting.<br />

Move to Protect Level:<br />

Displayed only when a password<br />

is set. Restricts moving to protect<br />

level.<br />

Operation/Adjustment Protect:<br />

Restricts displaying and<br />

modifying menus in operation,<br />

adjustment, and manual<br />

control levels.<br />

Initial Setting/<br />

Communications Protect:<br />

This protect level restricts movement<br />

to the initial setting, communications<br />

setting, and advanced<br />

function setting levels.<br />

Setting Change Protect:<br />

Protects changes to setups<br />

by operating the front panel<br />

keys.<br />

pfpt PF Key Protect<br />

Restricts PF key operation<br />

off (<strong>E5AN</strong>/EN-H only)<br />

M<br />

Parameter Mask Enable:<br />

pmsk Displayed only when a<br />

on parameter mask is set.<br />

M<br />

Password to Move to<br />

prlp Protect Level:<br />

0 Password setting<br />

M<br />

Press the O Key for at least 1 s.<br />

Press the O Key for at least 3 s.<br />

Other than the Auto/<strong>Manual</strong> Switch display<br />

Press the O Key less than 1 s.<br />

Communications<br />

Setting Level<br />

Displayed only for models with communications. Changes<br />

are effective after cycling power or after a software reset.<br />

Protocol Setting:<br />

psel Switches between<br />

CompoWay/F (SYScwf<br />

WAY) and Modbus.<br />

M<br />

u-no Communications Unit No.<br />

1<br />

M<br />

bps<br />

9.6<br />

M<br />

len 7<br />

M<br />

Communications<br />

sbit Stop Bits<br />

2<br />

M<br />

prty<br />

even<br />

M<br />

sdwt<br />

20<br />

M<br />

Communications<br />

Baud Rate<br />

CompoWay/F<br />

(SYSWAY) only<br />

Communications<br />

Data Length<br />

Communications Parity<br />

Send Data Wait Time<br />

Initial Setting Level<br />

Press the O Key less than 1 s.<br />

in-t<br />

5<br />

M<br />

in-h<br />

100<br />

M<br />

in-l<br />

0<br />

M<br />

dp<br />

0<br />

M<br />

d-u c<br />

M<br />

c sl-h<br />

1300.0<br />

M<br />

sl-l SP Lower Limit<br />

-200.0<br />

M<br />

cntl PID ON/OFF<br />

pid<br />

M<br />

Standard or<br />

s-hc Heating/Cooling<br />

stnd<br />

M<br />

ST (Self-tuning)<br />

st<br />

on<br />

M<br />

c<br />

ptrn<br />

off<br />

M<br />

pbnk<br />

7<br />

M<br />

cp<br />

20<br />

M<br />

c-cp<br />

20<br />

M<br />

orev<br />

or-r<br />

M<br />

alt1<br />

2<br />

M<br />

c<br />

alh1 Alarm 1<br />

Hysteresis<br />

0.2<br />

M<br />

Input Type<br />

Scaling Upper Limit<br />

Scaling Lower Limit<br />

Decimal Point<br />

For input type of analog<br />

Temperature Unit<br />

°C, °F<br />

For input type of<br />

temperature<br />

SP Upper Limit<br />

Limit the set point<br />

For input type of<br />

temperature, standard<br />

control, or PID<br />

Program Pattern<br />

Valid Program Bank<br />

When assigning PID or<br />

control output to ON/OFF<br />

output<br />

Control Period (Heating)<br />

Set the ON/OFF<br />

output cycle.<br />

Control Period (Cooling)<br />

Direct/Reverse Operation<br />

Alarm 1 Type<br />

alt2 Alarm 2 Type<br />

2<br />

M<br />

Alarm 2<br />

alh2<br />

Hysteresis<br />

0.2<br />

M<br />

Alarm 3 Type<br />

alt3<br />

2<br />

M<br />

Alarm 3<br />

alh3<br />

Hysteresis<br />

0.2<br />

c<br />

c<br />

M<br />

tr-t<br />

off<br />

M<br />

tr-h Transfer Output<br />

Upper Limit<br />

100.0<br />

M<br />

tr-l Transfer Output<br />

Lower Limit<br />

0.0<br />

M<br />

Linear Current Output<br />

o1-t<br />

4-20<br />

Linear output<br />

M<br />

ev-b<br />

1<br />

M<br />

ev-1<br />

none<br />

M<br />

ev-2<br />

stop<br />

M<br />

ev-3<br />

Event Input<br />

Assignment 3<br />

none<br />

M<br />

ev-4<br />

Event Input<br />

Assignment 4<br />

none<br />

M<br />

clfl<br />

flot<br />

M<br />

Transfer Output Type<br />

Linear output<br />

Bank Numbers Used<br />

Event Input<br />

Assignment 1<br />

Event Input<br />

Assignment 2<br />

Closed/Floating<br />

calb Motor Calibration<br />

off<br />

M<br />

mot Travel Time<br />

30<br />

M<br />

sqr Extraction of Square<br />

Root Enable<br />

off<br />

M<br />

Move to Advanced Function<br />

Setting Level:<br />

amov Displayed when initial set-<br />

0 ting/ communications protect<br />

is set to 0.<br />

M<br />

Move by setting password (−169).<br />