Calibrating Analog Input (Analog Input) Section 6-5<br />

6-5 Calibrating Analog Input (Analog Input)<br />

6-5-1 Calibrating a Current Input<br />

290<br />

p-10<br />

4543<br />

str no<br />

adj 30<br />

a-20<br />

c8e7<br />

6. When the M Key is pressed, the status changes as shown to the left.<br />

Set the 6-dial to 10 Ω.<br />

Allow the count value on the No. 2 display to fully stabilize, then press the<br />

D Key to temporarily register the calibration settings.<br />

If this count value is outside of the specified range, the No. 2 display will<br />

flash and the count value will not be temporarily registered.<br />

7. When the M Key is pressed, the status changes as shown to the left.<br />

The data to be temporarily registered is not displayed if it is not complete.<br />

Press the U Key. The No. 2 display changes to yes. Release the key and<br />

wait two seconds or press the M Key. This stores the temporarily registered<br />

calibration data to EEPROM.<br />

To cancel the saving of temporarily registered calibration data to EE-<br />

PROM, press the M Key (while no is displayed in the No. 2 display) without<br />

pressing the U Key.<br />

8. The calibration mode is quit by turning the power OFF.<br />

For <strong>Controllers</strong> that have a transfer output (<strong>E5AN</strong>/EN-H@@F), transfer output<br />

calibration continues to be performed. For details on the settings, refer to 6-6<br />

Calibrating the Transfer Output on page 292.<br />

In this example, calibration is shown for a Controller with a current input set as<br />

the input type.<br />

1,2,3... 1. Connect the power supply.<br />

2. Connect an STV and DMM to the current input terminals, as shown in the<br />

following diagram.<br />

E5CN-H<br />

<strong>E5AN</strong>/EN-H<br />

STV<br />

DMM<br />

9<br />

Input power supply<br />

10<br />

3<br />

4<br />

+<br />

−<br />

STV<br />

DMM<br />

1<br />

Input power supply<br />

2<br />

3. Turn the power ON.<br />

4. Move to the calibration level.<br />

This starts the 30-minute aging timer. This timer provides an approximate<br />

timer for aging. After 30 minutes have elapsed, the No. 2 display changes<br />

to 0. You can advance to the next step in this procedure even if 0 is not<br />

displayed.<br />

5. When the M Key is pressed, the status changes as shown to the left.<br />

The No. 2 display at this time shows the currently entered count value in<br />

hexadecimal. Set the STV to 20 mA.<br />

Allow the count value on the No. 2 display to fully stabilize, then press the<br />

D Key to temporarily register the calibration settings.<br />

If this count value is outside of the specified range, the No. 2 display will<br />

flash and the count value will not be temporarily registered.<br />

18<br />