Using a Remote SP Section 4-23<br />

4-23 Using a Remote SP<br />

Remote SP Scaling<br />

The remote SP function scales a remote SP input (4 to 20 mA) to the remote<br />

SP upper and lower limits, and takes it as the set point. (This function is supported<br />

by the <strong>E5AN</strong>-H and <strong>E5EN</strong>-H only.)<br />

Set the Remote SP Enable parameter (advanced function setting level) to ON,<br />

and use an event input or an operation command to select the remote SP.<br />

Parameter Setting range Unit Default<br />

Remote SP Enable OFF: Disable, ON: Enable None OFF<br />

Remote SP Upper Limit SP lower limit to SP upper limit EU 1300.0<br />

Remote SP Lower Limit SP lower limit to SP upper limit EU −200.0<br />

SP Tracking OFF: Disable, ON: Enable None OFF<br />

Remote SP Input Error<br />

Output<br />

OFF: Disable, ON: Enable None OFF<br />

SP Mode LSP: Local SP, RSP: Remote SP None LSP<br />

Remote SP Monitor Remote SP lower limit to remote SP<br />

upper limit<br />

EU ---<br />

Precautions<br />

When the ST (self-tuning) parameter is turned ON, the SP Mode parameter<br />

is forcibly set to LSP.<br />

The remote SP input is not accepted during autotuning. Autotuning is executed<br />

for the remote SP at the beginning of autotuning.<br />

Changes in the remote SP value are not used as conditions for resetting<br />

the standby sequence.<br />

The remote SP input (4 to 20 mA) can be scaled to match the PV input<br />

range, based on the Remote SP Upper Limit and Remote SP Lower Limit<br />

parameter settings.<br />

The remote SP input can be input in a range of −10% to 110% of 4 to 20<br />

mA. Input values outside of this range treated as out-of-range input values<br />

(RSP input error) and clamped to the upper or lower limit. In SP<br />

mode, the RSP single indicator will flash, and in local SP mode the No. 2<br />

indicator for the Remote SP Monitor will flash.<br />

An alarm can be output if an RSP input error occurs by setting the<br />

Remote SP Input Error Output parameter to ON.<br />

RSP (%)<br />

Remote SP upper limit<br />

Remote SP lower limit<br />

4.0 21.6<br />

2.4 (−10%)<br />

20.0 (110%)<br />

Input (mA)<br />

155