Performing <strong>Manual</strong> Control Section 4-13<br />

<strong>Manual</strong> MV Limit<br />

Enable<br />

Moving from the<br />

Operation Level to the<br />

<strong>Manual</strong> Control Level<br />

C<br />

Press O key for at least 1 s.<br />

25.0<br />

20.0<br />

PV/MV<br />

<strong>Manual</strong> Control Level<br />

(2) For <strong>Manual</strong> MV Limit Enable, this value will be between the MV upper limit<br />

and the MV lower limit.<br />

(3) This setting is enabled only when the Direct Setting of Position Proportional<br />

MV parameter is set to ON.<br />

When the <strong>Manual</strong> MV Limit Enable parameter is set to ON (enabled), the MV<br />

limits will function and the setting range for the <strong>Manual</strong> MV parameter will be<br />

between the MV upper limit and the MV lower limit. When the parameter is set<br />

to OFF (disabled), MV limits will not function.<br />

Parameter name Setting range Default<br />

<strong>Manual</strong> MV Limit<br />

Enable<br />

OFF: Disabled, ON: Enabled ON<br />

When the O Key is pressed for at least 3 seconds in the operation level's<br />

auto/manual switching display, the manual mode will be entered and the<br />

manual control level will be displayed. It is not possible to move to any displays<br />

except for the PV/MV parameter during manual operation. Press the<br />

O Key for at least one second from the PV/MV parameter display in manual<br />

control level to return to automatic mode and display the top parameter<br />

in the operation level.<br />

a-m<br />

Press O key for at least<br />

3 s.<br />

a-m display flashes for<br />

at least 1 s.<br />

Operation Level<br />

C<br />

C<br />

25.0<br />

M<br />

25.0<br />

100.0<br />

M<br />

a-m<br />

M<br />

bank 0<br />

M<br />

If an event input is set to MANU (auto/manual), the Auto/<strong>Manual</strong> Switch<br />

parameter will not be displayed. Use the event input to switch between<br />

automatic and manual modes.<br />

PV<br />

PV/SP<br />

Auto/<strong>Manual</strong> Switch<br />

Bank No.<br />

121