Adjustment Level Section 5-4<br />

db Position Proportional Dead Band<br />

Function<br />

Setting<br />

See<br />

This parameter sets the output hold interval (the ON/OFF switching interval<br />

between the open and close outputs) for position-proportional control.<br />

Setting range Unit Default<br />

Position proportional (close):<br />

0.1 to 10.0<br />

% 4.0<br />

Position proportional (floating):<br />

0.1 to 10.0<br />

% 2.0<br />

■ Related Parameters<br />

oc-h Open/Close Hysteresis<br />

Function<br />

Setting<br />

See<br />

Open/close hysteresis (adjustment level): Page 207<br />

This parameter provides hysteresis in position-proportional control when<br />

the open and close outputs are switched ON or OFF.<br />

Setting range Unit Default<br />

0.1 to 20.0 % 0.8<br />

■ Related Parameters<br />

Position-proportional control must be<br />

supported.<br />

Position-proportional control must be<br />

supported.<br />

Position proportional dead band (adjustment level): Page 207<br />

sqrp Extraction of Square Root Low-cut Point<br />

Function<br />

The input type must be an analog<br />

input, and the Extraction of Square<br />

Root Enable parameter must be set<br />

to ON.<br />

This parameter sets the extraction of square root low-cut point used for<br />

the inputs. The data after extracting the square root is shown below.<br />

207