Alarm 1Type alt1 0: Alarm function OFF<br />

2 None<br />

1: Upper and lower-limit<br />

alarm<br />

2: Upper-limit alarm<br />

3: Lower-limit alarm<br />

4: Upper and lower-limit<br />

range alarm<br />

5: Upper and lower-limit<br />

alarm with standby<br />

sequence<br />

6: Upper-limit alarm with<br />

standby sequence<br />

7: Lower-limit alarm with<br />

standby sequence<br />

8: Absolute-value upper-limit<br />

alarm<br />

9: Absolute-value lower-limit<br />

alarm<br />

Alarm 1 Hysteresis alh1<br />

10: Absolute-value upper-limit<br />

alarm with standby<br />

sequence<br />

11: Absolute-value lower-limit<br />

alarm with standby<br />

sequence<br />

12: LBA (Loop Burnout Alarm)<br />

13: PV change rate alarm<br />

14: Remote SP absolute<br />

value upper limit alarm<br />

(See note 1.)<br />

15: Remote SP absolute<br />

value lower limit alarm<br />

(See note 1.)<br />

Temperature input: 0.1 to<br />

3240.0<br />

0.2 °C or °F<br />

Analog input: 0.01 to 99.99 0.02 %FS<br />

Alarm 2 Type alt2 Same settings as the alarm 1<br />

type.<br />

Note The 12: LBA (Loop<br />

Burnout Alarm) setting<br />

cannot be used.<br />

2 None<br />

Alarm 2 Hysteresis alh2 Temperature input: 0.1 to<br />

3240.0<br />

0.2 °C or °F<br />

Analog input: 0.01 to 99.99 0.02 %FS<br />

Alarm 3 Type alt3 Same settings as the alarm 2<br />

type<br />

2 None<br />

Alarm 3 Hysteresis alh3 Temperature input: 0.1 to<br />

3240.0<br />

0.2 °C or °F<br />

Analog input: 0.01 to 99.99 0.02 %FS<br />

Transfer Output Type tr-t OFF: OFF<br />

SP: Set point (See note 2.)<br />

SP-M: Ramp set point<br />

PV: Process value<br />

MV: Manipulated variable<br />

(heating) (See note 3.)<br />

C-MV: Manipulated variable<br />

(cooling) (See note 4.)<br />

V-M: Valve Opening (See<br />

note 5.)<br />

Transfer Output<br />

Upper Limit<br />

320<br />

off<br />

sp<br />

sp-m<br />

pv<br />

mv<br />

c-mv<br />

v-m<br />

OFF None<br />

tr-h See note 6. See note 6. See note 6.<br />

Appendix<br />

Parameters Characters Setting (monitor) value Display Default Unit Set value