Initial Setting Examples Section 3-1<br />

3-1 Initial Setting Examples<br />

Explanation of Examples<br />

Example 1<br />

46<br />

Initial hardware setup, including the sensor input type, alarm types, control<br />

periods, and other settings is done using parameter displays. The O and M<br />

Keys are used to switch between parameters, and the amount of time that you<br />

press the keys determines which parameter you move to.<br />

This section describes 3 typical examples.<br />

Changing Parameters<br />

in-t 0<br />

M<br />

cntl<br />

pid<br />

in-h<br />

100 M<br />

in-l<br />

0 M<br />

cntl<br />

Input type: 5 (K thermocouple,<br />

−200.0°C to 1,300.0°C)<br />

Control method: ON/OFF control<br />

Alarm type: 2 (upper limit)<br />

Alarm value 1: 20°C (deviation)<br />

Set point: 100°C<br />

pid<br />

Setup Procedure<br />

Initial Setting<br />

Level<br />

Operation<br />

Level<br />

Power ON<br />

Set input<br />

specifications<br />

Set control<br />

specifications<br />

Set alarm type<br />

Set alarm values<br />

Start operation<br />

A image means that there are parameters.<br />

Continue pressing the M key to change parameters<br />

until you reach the intended parameter.<br />

Changing Numbers<br />

C<br />

25.0<br />

0.0<br />

Numeric data and selections in each<br />

screen can be changed by using the<br />

U and D keys.<br />

Operation<br />

Level<br />

Initial Setting<br />

Level<br />

Check input type.<br />

Check that<br />

control method is<br />

ON/OFF control.<br />

Check alarm type.<br />

Operation<br />

Level<br />

Use the U and<br />

D keys to set the<br />

SP to 100°C.<br />

Confirm that<br />

control is running.<br />

Use the U and<br />

D keys to set the<br />

alarm value to<br />

20°C.<br />

Power ON<br />

C<br />

C<br />

C<br />

25.0<br />

0.0<br />

25.0<br />

100.0<br />

M<br />

r-s<br />

run<br />

M<br />

al-1<br />

20.0<br />

M<br />

PV/SP<br />

Press the O key for<br />

at least 3 s.<br />

Control stops.<br />

in-t<br />

5<br />

M<br />

Input Type: 5<br />

cntl<br />

onof<br />

ON/OFF<br />

control:<br />

PID<br />

onof<br />

pid<br />

M control:<br />

alt1<br />

2<br />

M<br />

Alarm 1 Type: 2<br />

Press the O key for<br />

at least 1 s.<br />

Control starts.<br />

PV/SP:<br />

Running<br />

Stopped:<br />

Start operation.<br />

100.0<br />

run<br />

stop<br />

Alarm Value 1: 20.0