Using the Transfer Output Section 4-14<br />

Output current (mA)<br />

20<br />

4<br />

0<br />

10<br />

Transfer output<br />

lower limit<br />

90 100<br />

Transfer output<br />

upper limit<br />

MV (%)<br />

(The above graph is for when the linear current output is set to 4 to 20 mA.)<br />

Operating Procedure The following procedure sets the transfer output for an SP range of −50 to<br />

200.<br />

Operation Level<br />

C<br />

25.0<br />

100.0<br />

Initial Setting Level 1. Press the O Key for at least three seconds to move from the operation<br />

Input Type<br />

level to the initial setting level.<br />

in-t 5<br />

Initial Setting Level 2. Select the Transfer Output Type parameter by pressing the M Key.<br />

tr-t<br />

off<br />

tr-t sp<br />

PV/SP<br />

Transfer Output<br />

Type<br />

3. Press the U Key to select sp (set point).<br />

Initial Setting Level 4. Select the Transfer Output Upper Limit parameter by pressing the M Key.<br />

C<br />

Transfer Output<br />

tr-h Upper Limit<br />

1300.0<br />

C<br />

tr-h<br />

200.0<br />

5. Use the D Key to set the parameter to 200.0. The default is 1300.0.<br />

Initial Setting Level 6. Select the Transfer Output Lower Limit parameter by pressing the M Key.<br />

C<br />

Transfer Output<br />

tr-l Lower Limit<br />

-200.0<br />