Position-proportional Control Section 4-24<br />

4-24 Position-proportional Control<br />

Closed Control<br />

Floating Control<br />

The control method used to adjust the opening and closing of a valve with a<br />

control motor is called "position-proportional control" or "ON/OFF servo control."<br />

Either closed control or floating control can be selected for position-proportional<br />

control. Only models that support position-proportional control<br />

(<strong>E5AN</strong>/EN-HPRR@) can be used for position-proportional control. In addition,<br />

the following functions are disabled when using position-proportional control.<br />

ST<br />

LBA<br />

Heater burnout, heater short, and heater overcurrent alarms<br />

ON/OFF control<br />

P and PD control (for floating control only)<br />

40% AT (for floating control only)<br />

Closed control provides control using feedback on the valve opening by connecting<br />

a potentiometer.<br />

Floating control provides control without using feedback on the valve opening,<br />

so control is still possible even if a potentiometer is not connected. With floating<br />

control, the expected valve opening is calculated from the travel time, and<br />

that value is treated as the valve opening for executing control outputs.<br />

If there is no FB input, then even if the Closed/Floating parameter is set to<br />

Closed the parameter will be disabled and floating control will be executed.<br />

Parameter Setting range Unit Default<br />

Travel Time 1 to 999 s 30<br />

Motor Calibration and Travel Time<br />

Calibrate the motor when a potentiometer is connected, such as in closed<br />

control or in floating control for monitoring valve opening. The fully closed and<br />

fully open valve positions will be calibrated and the travel time, i.e., the time<br />

from the fully open to the fully closed position, will be automatically measured<br />

and set. Set the Motor Calibration parameter to ON to execute the motor calibration.<br />

The setting will be automatically changed OFF when the calibration<br />

has been completed.<br />

For floating control (i.e., without a potentiometer connection), it is necessary<br />

to manually set the travel time. Set the Travel Time parameter to the time from<br />

the fully open to the fully closed valve position.<br />

Parameter Setting range Unit Default<br />

Motor Calibration OFF, ON --- OFF<br />

157