Loop Burnout Alarm Section 4-12<br />

Operation Level 9. Press the O Key for at least one second to move from the initial setting<br />

C<br />

PV/SP<br />

level to the operation level.<br />

4-12 Loop Burnout Alarm<br />

4-12-1 Loop Burnout Alarm (LBA)<br />

114<br />

25.0<br />

100.0<br />

Set point<br />

LBA detection<br />

time<br />

(1)<br />

LBA OFF<br />

The loop burnout alarm can be used only with standard models.<br />

With a loop burnout alarm, there is assumed to be an error in the control<br />

loop if the control deviation (SP − PV) is greater than the threshold set in<br />

the LBA Level parameter and if the control deviation is not reduced by at<br />

least the value set in the LBA Detection Band parameter within the LBA<br />

detection time.<br />

Loop burnout alarms are detected at the following times.<br />

Area where LBA<br />

is not detected<br />

LBA detection<br />

time<br />

LBA band LBA band<br />

LBA band<br />

LBA detection<br />

time<br />

(2) (3) (4) (5) (6) (7)<br />

LBA ON LBA OFF<br />

LBA detection<br />

time<br />

LBA ON<br />

LBA level<br />

LBA level<br />

If the control deviation is reduced in the area between 1 and 2 (i.e., the set<br />

point is approached) and the amount the control deviation is reduced is at<br />

least equal to the LBA band, the loop burnout alarm will remain OFF.<br />

The process value is within the LBA level between 3 and 4, and thus loop<br />

burnout alarms will not be detected. (The loop burnout alarm will remain OFF.)<br />

If the process value is outside the LBA level between 4 and 5 and the control<br />

deviation is not reduced by at least the LBA band within the LBA detection<br />

time, the loop burnout alarm will turn ON.<br />

If the control deviation is reduced in the area between 5 and 6 (i.e., the set<br />

point is approached) and the amount the control deviation is reduced is at<br />

least equal to the LBA band, the loop burnout alarm will turn OFF.<br />

If the control deviation is reduced in the area between 6 and 7 (i.e., the set<br />

point is approached) and the amount the control deviation is reduced is less<br />

than the LBA band, the loop burnout alarm will turn ON.<br />

If the LBA detection time, LBA level, LBA detection band, and PID settings<br />

are not appropriate, alarms may be detected inappropriately or<br />

alarms may not be output when necessary.<br />

Loop burnout alarms may be detected if unexpectedly large disturbances<br />

occur continuously and a large deviation does not decrease.