Operation Level Section 5-3<br />

al1h Alarm Value Upper Limit 1 Alarm 1 must be assigned.<br />

al1l Alarm Value Lower Limit 1<br />

Function<br />

Setting<br />

See<br />

The alarm 1 type must not be 1, 4, or<br />

5.<br />

These parameters independently set the alarm value upper and lower limits<br />

when the mode for setting the upper and lower limits is selected for the Alarm<br />

1 Type parameter (initial setting level).<br />

This parameter sets the upper and lower limit values of alarm 1.<br />

During temperature input, the decimal point position depends on the currently<br />

selected sensor, and during analog input it depends on the Decimal<br />

Point parameter setting.<br />

The set value is saved in the Alarm Value Upper Limit 1 and Alarm Value<br />

Lower Limit 1 parameters in the current bank.<br />

Setting range Unit Default<br />

−19999 to 32400 EU 0.0<br />

■ Related Parameters<br />

Input type: Page 224, Scaling upper limit, Scaling lower limit, Decimal point:<br />

Page 226, Alarm 1 type: Page 231 (initial setting level), Standby sequence<br />

reset: Page 244, Auxiliary output * open in alarm: Page 245, Alarm 1 hysteresis:<br />

Page 233, Alarm 1 latch: Page 250 (advanced function setting level)<br />

Bank * alarm value upper limit 1, Bank * alarm value lower limit 1 (bank setting<br />

level): Page 212<br />

al2h Alarm Value Upper Limit 2 Alarm 2 must be assigned.<br />

al2l Alarm Value Lower Limit 2<br />

Function<br />

Setting<br />

The alarm 2 type must not be 1, 4, or<br />

5.<br />

These parameters independently set the alarm value upper and lower limits<br />

when the mode for setting the upper and lower limits is selected for the Alarm<br />

2 Type parameter (initial setting level).<br />

This parameter sets the upper and lower limit values of alarm 2.<br />

During temperature input, the decimal point position depends on the currently<br />

selected sensor, and during analog input it depends on the Decimal<br />

Point parameter setting.<br />

The set value is saved in the Alarm Value Upper Limit 2 and Alarm Value<br />

Lower Limit 2 parameters in the current bank.<br />

Setting range Unit Default<br />

−1999 to 9999 EU 0<br />

187