Advanced Function Setting Level Section 5-10<br />

och Heater Overcurrent Hysteresis<br />

Function<br />

Setting<br />

See<br />

pf PF Setting<br />

Function<br />

Setting<br />

This parameter sets the hysteresis for heater overcurrent detection.<br />

■ Related Parameters<br />

Heater overcurrent use (advanced function setting level): Page 272<br />

This parameter sets the function of the PF Key.<br />

The default setting is A-M (Auto/<strong>Manual</strong>).<br />

Heater burnout, HS alarms, and<br />

heater overcurrent detection must be<br />

supported, and alarm 1 must be<br />

assigned. The Heater Overcurrent<br />

Use parameter must be set to ON,<br />

and the Heater Overcurrent Latch<br />

parameter must be set to OFF.<br />

Setting range Unit Default<br />

0.1 to 50.0 A 0.1<br />

The PF Key must be supported<br />

(<strong>E5AN</strong>/EN-H).<br />

Set value Setting Function<br />

OFF: off Disabled Does not operate as a function key.<br />

RUN: run RUN Specifies RUN status.<br />

STOP: stop STOP Specifies STOP status.<br />

R-S: r-s Reversing RUN/STOP Specifies reversing RUN/STOP opera-<br />

operation<br />

tion status.<br />

AT-2: at-2 100%AT<br />

Specifies reversing 100% AT Execute/<br />

Execute/Cancel<br />

Cancel status. (See note 1.)<br />

AT-1: at-1 40%AT<br />

Specifies reversing 40% AT Execute/<br />

Execute/Cancel<br />

Cancel status. (See notes 1 and 2.)<br />

LAT: lat Alarm Latch Cancel Specifies canceling alarm latches. (See<br />

note 3.)<br />

A-M: a-m Auto/<strong>Manual</strong> Specifies reversing Auto/<strong>Manual</strong> status<br />

(See note 4.)<br />

PFDP: pfdp Monitor/Setting Item Specifies the monitor/setting item display.<br />

Select the monitor/setting item<br />

using the Monitor/Setting Item 1 to 5<br />

parameters (advanced function setting<br />

level).<br />

BANK: bank Bank No. Specifies switching to the bank number<br />

+ 1.<br />

Note (1) When AT cancel is specified, it means that AT is cancelled regardless of<br />

whether the AT currently being executed is 100% AT or 40% AT.<br />