Initial Setting Level Section 5-9<br />

cntl PID ON/OFF<br />

Function<br />

Setting<br />

See<br />

228<br />

This parameter selects 2-PID control or ON/OFF control.<br />

The auto-tuning and self-tuning functions can be used in 2-PID control.<br />

Setting range Default<br />

pid: 2-PID, onof: ON/OFF pid<br />

■ Related Parameters<br />

s-hc Standard or Heating/Cooling<br />

Function<br />

Setting<br />

See<br />

st ST (self-tuning)<br />

Function<br />

AT execute/cancel: Page 192, <strong>Manual</strong> reset, Hysteresis (heating), and Hysteresis<br />

(cooling): Page 202 (adjustment level)<br />

ST stable range (advanced function setting level): Page 247<br />

This parameter selects standard control or heating/cooling control.<br />

When heating/cooling control is selected for the E5CN-H (for a model<br />

which does not support control output 2), the auxiliary output 2 terminal<br />

(SUB2) is assigned as the control output (cooling).<br />

Setting range Default<br />

stnd: Standard, h-c: Heating/cooling stnd<br />

■ Related Parameters<br />

MV monitor (heating): Page 188, MV monitor (cooling): Page 189 (operation<br />

level)<br />

Cooling coefficient, Dead band: Page 201, Hysteresis (heating), Hysteresis<br />

(cooling): Page 202 (adjustment level)<br />

Control period (heat), Control period (cool) (initial setting level): Page 230<br />

Control output 1 assignment: Page 261, Control output 2 assignment, Auxiliary<br />

output 1 assignment: Page 263, Auxiliary output 2 assignment: Page 264,<br />

Auxiliary output 3 assignment: Page 265 (advanced function setting level)<br />

The control must be set to a temperature<br />

input, standard control, and 2-<br />

PID control.<br />

The ST (self-tuning) function executes tuning from the start of program<br />

execution to calculate PID constants matched to the control target. When<br />

the ST function is in operation, be sure to turn ON the power supply of the<br />

load connected to the control output simultaneously with or before starting<br />

Controller operation.