Using the Simple Program Function Section 4-16<br />

Operation When<br />

Power Is Turned ON<br />

136<br />

Note If the wait band is set to OFF, the wait band will be treated as infinity and the<br />

timer will measure time continuously after changing from RSET to STRT.<br />

4-16-2 Operation at the Program End<br />

The following will occur if a power interruption occurs during execution of a<br />

simple program:<br />

The program start (RSET/STRT) and RUN/STOP status from before the<br />

power interruption will be held.<br />

The timer value for the Soak Time parameter will be reset.<br />

Therefore, when a power interruption occurs, the timer value for the Soak<br />

Time parameter will not be correct. In addition, if starting the program is<br />

assigned to an event input, the event input status when a power interruption<br />

occurs will be the program start status from just before the power interruption.<br />

The following table shows operation when program operation ends, according<br />

to the Program Pattern parameter setting.<br />

Program Pattern Executed bank<br />

No.<br />

STOP End bank number<br />

held<br />

Note (1) The bank number can be changed even during program operation by using<br />

either an event inputs or key operation.<br />

(2) The bank number is initialized to 0 when the program pattern is changed.<br />

Display at the Program End<br />

When the program ends, the process value will be displayed on the No. 1 display<br />

(see note) and the set point and “end” will be alternately displayed on the<br />

No. 2 display at 0.5 s intervals.<br />

Note One of the following displays: PV/SP, PV only, or PV/MV.<br />

Program End Output<br />

RUN/STOP status Program end<br />

output<br />

STOP command ON<br />

executed.<br />

CONT RUN continues.<br />

LOOP --- --- ---<br />

120.1 Displayed alternately.<br />

end 120.0<br />

When the Program Pattern parameter is changed from OFF to STOP, CONT,<br />

or LOOP, the Auxiliary Output 1 Assignment parameter will automatically be<br />

set to the end output. Conversely, when the Program Pattern parameter is<br />

changed from STOP, CONT, or LOOP to OFF, the Alarm 1 Output Assignment<br />

parameter will automatically be initialized to ALM1. The output assignment<br />

parameters can also be used to assign the program end output to any output.<br />

A program end output is also provided in communications status.<br />

Clearing the Program End Status<br />

The program END output and display will be cleared when the Program Start<br />

parameter is changed from STRT to RSET. The setting is changed from STRT<br />

to RSET while the Program Start parameter is displayed.