PID Setting Level Section 5-6<br />

Setting<br />

See<br />

*.aut<br />

Function<br />

Setting<br />

See<br />

218<br />

MV Upper Limit<br />

The setting range depends on whether standard, position-proportional<br />

(closed) control, or heating/cooling control is used. In addition, the cooling<br />

MV during heating/cooling control is expressed as a negative value.<br />

Control method Setting range Unit Default<br />

Standard MV lower limit + 0.1 to 105.0 % 105.0<br />

Heating/cooling 0.0 to 105.0<br />

Position-proportional<br />

(closed)<br />

MV lower limit + 0.1 to 105.0<br />

MV Lower Limit<br />

The setting range depends on whether standard, position-proportional<br />

(closed) control, or heating/cooling control is used. In addition, the cooling<br />

MV during heating/cooling control is expressed as a negative value.<br />

Control method Setting range Unit Default<br />

Standard −5.0 to MV lower limit - 0.1 % −5.0<br />

Heating/cooling −105.0 to 0.0 −105.0<br />

Position-proportional<br />

(closed)<br />

−5.0 to MV upper limit - 0.1 −5.0<br />

■ Related Parameters<br />

PID ON/OFF: Page 228<br />

ST (initial setting level): Page 228<br />

PID * Automatic Selection Range Upper<br />

Limit (*: 1 to 8)<br />

2-PID control must be used.<br />

These parameters set the upper limit for each PID set when PID sets are<br />

selected automatically.<br />

These parameters are used to set the automatic selection range upper<br />

limits for PID sets 1 to 8.<br />

The sensor setting range for PID set 8 is 32,400 EU for temperature<br />

inputs and 105.0% for analog inputs. This parameter does not need to be<br />

set.<br />

These values apply to the PV (process value), DV (deviation), or SP (set<br />

point) set in the PID Set Automatic Selection Data parameter. The default<br />

setting is PV.<br />

Setting range Unit Default<br />

Temperature: −19,999 to<br />

32,400<br />

EU 1320.0<br />

Analog: −5.0 to 105.0 % 105.0<br />

■ Related Parameters<br />

PID set automatic selection data (advanced function setting level): Page 269