Setting Output Specifications Section 3-5<br />

Initial Setting Level 3. Press the U Key to set the parameter to h-c.<br />

5-hc<br />

h-c<br />

amov 0<br />

Move to Advanced<br />

Function<br />

Setting Level<br />

Note The following output assignments do not need to be set because they<br />

are set automatically by changing the control mode, but they are<br />

shown here as a reference for checking the assignments for each output.<br />

4. Select the Move to Advanced Function Setting Level parameter by pressing<br />

the M Key. (For details on moving between levels, refer to 4-8 Moving<br />

to the Advanced Function Setting Level.)<br />

Advanced Function Setting Level 5. Press the D Key to enter the password (“−169”), and move from the initial<br />

Parameter<br />

Initialization<br />

setting level to the advanced function setting level.<br />

init<br />

off<br />

Advanced Function Setting Level 6. Select the Control Output 1 Assignment parameter by pressing the M<br />

Control Output<br />

1 Assignment<br />

Key.<br />

out1 o<br />

out1 o<br />

7. Press the U or D Key to set o.<br />

(The default is o.)<br />

Advanced Function Setting Level 8. Select the Control Output 2 Assignment parameter by pressing the M<br />

Control Output<br />

2 Assignment<br />

Key.<br />

out2<br />

c-o<br />

out2<br />

c-o<br />

9. Press the U or D Key to set c-o.<br />

(When h-c is selected for the Standard or Heating/Cooling parameter,<br />

the setting will be c-o.)<br />

Advanced Function Setting Level 10. Select the Auxiliary Output 1 Assignment parameter by pressing the M<br />

Auxiliary Output<br />

1 Assignment<br />

Key.<br />

sub1<br />

alm1<br />

sub1<br />

alm1<br />

11. Press the U or D Key to set alm1.<br />

(The default is alm1.)<br />

Advanced Function Setting Level 12. Select the Auxiliary Output 2 Assignment parameter by pressing the M<br />

Auxiliary Output<br />

2 Assignment<br />

Key.<br />

sub2<br />

alm2<br />

sub2<br />

alm2<br />

13. Press the U or D Key to set alm2.<br />

(The default is alm2.)<br />

55