05.03.2013 Views

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

E5CNH E5AN-H E5EN-H Digital Controllers User's Manual - OMRON

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Adjustment Level Section 5-4<br />

5-4 Adjustment Level<br />

190<br />

This level is for executing AT (auto-tuning) and other operations, and for set<br />

control parameters.<br />

This <strong>Digital</strong> <strong>Controllers</strong> the basic Controller parameters for PID control (proportional<br />

band, integral time, derivative time) and heating/cooling control.<br />

Power ON<br />

Operation Level<br />

PID Setting<br />

Level<br />

Press the O Key<br />

for at least 1 s.<br />

Adjustment<br />

Level<br />

Bank Setting<br />

Level<br />

Control in progress<br />

To move to the adjustment level from the operation level, press the O Key<br />

once.<br />

The following parameters are displayed for <strong>Controllers</strong> with CT Inputs:<br />

Heater current monitors, Leakage current monitors, heater burnout detections,<br />

HS alarms, and heater overcurrent detections.<br />

Adjustment level parameters can be changed after setting the Operation/<br />

Adjustment Protect parameter to 0. Displays and changing levels are not<br />

possible if the Operation/Adjustment Protect parameter is set to 1 to 3.<br />

Protection is set in the protect level.