Adjustment Level Section 5-4<br />

See<br />

■ Related Parameters<br />

ins Temperature Input Shift<br />

Function<br />

Setting<br />

See<br />

Leakage current 2 monitor (adjustment level): Page 198<br />

HS alarm use, HS alarm latch, HS alarm hysteresis (advanced function setting<br />

level): Page 257<br />

Sometimes an error occurs between the set point and the actual temperature.<br />

To offset this, a compensated value can be obtained by adding an input shift<br />

value to the input. The compensated value is displayed as the measurement<br />

value and used for control.<br />

The entire input range is shifted by a fixed rate (1-point shift). If the input shift<br />

value is set to −1°C, control will be performed for a value 1°C lower than the<br />

measured temperature.<br />

Setting range Unit Default<br />

−199.99 to 324.00 °C or °F 0.00<br />

■ Related Parameters<br />

Input type (initial setting level): Page 224<br />

Input shift type (advanced function setting level): Page 256<br />

These parameters are used to shift the input temperature at two points: an<br />

upper-limit temperature and a lower-limit temperature (as opposed to the<br />

Temperature Input Shift parameter, which shifts the input temperature by setting<br />

the shift for only one point). A 2-point shift enables more accurate offset of<br />

the input range compared with a 1-point shift if the input shift values at the<br />

upper and lower limits differ.<br />

This parameter sets input shift values for the upper and lower limits (2-point<br />

shift) of the input range.<br />

■ Related Parameters<br />

Input type (initial setting level): Page 224<br />

Input shift type (advanced function setting level): Page 256<br />

The Input Type parameter must be<br />

set for a thermocouple or resistance<br />

thermometer, and the Input Shift<br />

Type parameter must be set to a<br />

one-point shift.<br />

insh Upper-limit Temperature Input Shift Value The Input Type parameter must be<br />

set for a thermocouple or resistance<br />

insl Lower-limit Temperature Input Shift Value<br />

Function<br />

Setting<br />

See<br />

Setting range Unit Default<br />

−199.99 to 324.00 °C or °F 0.00<br />

thermometer and the Input Shift Type<br />

parameter must be set to a 2-point<br />

shift.<br />

199