Advanced Function Setting Level Section 5-10<br />

pvdp PV Decimal Point Display<br />

Function<br />

Setting<br />

See<br />

276<br />

The display below the decimal point in the PV can be hidden for temperature<br />

inputs.<br />

The PV decimals below the decimal point can be hidden by setting the PV<br />

Decimal Point Display parameter to OFF. When this parameter is set to<br />

ON, the display below the decimal point will appear according to the input<br />

type setting.<br />

Setting range Default<br />

on: ON, off: OFF ON<br />

■ Related Parameters<br />

Input type (initial setting level): Page 224<br />

pvst PV Status Display Function<br />

Monitor<br />

See<br />

The PV in the No. 1 display for the PV/SP, PV, or PV/<strong>Manual</strong> MV (Valve<br />

Opening) Screen is alternately displayed in 0.5-s cycles with the control<br />

and alarm status specified for the PV status display function.<br />

■ Related Parameters<br />

Process value/set point, PV (operation level): Page 177<br />

PV/MV (manual MV) (manual control level): Page 221<br />

The input type must be set to temperature<br />

input.<br />

Monitor range Default<br />

off: No PV status display off<br />

manu: MANU is alternately displayed during manual control.<br />

stop: STOP is alternately displayed while operation is stopped.<br />

alm1: ALM1 is alternately displayed during Alarm 1 status.<br />

alm2: ALM2 is alternately displayed during Alarm 2 status.<br />

alm3: ALM3 is alternately displayed during Alarm 3 status.<br />

alm: ALM is alternately displayed when Alarm 1, 2, or 3 is set to ON.<br />

ha: HA is alternately displayed when a heater burnout alarm, HS alarm,<br />

or heater overcurrent alarm is ON.