Advanced Function Setting Level Section 5-10<br />

lba LBA Detection Time<br />

Function<br />

Setting<br />

See<br />

lbal LBA Level<br />

Function<br />

Setting<br />

See<br />

This parameter enables or disables the LBA function and sets the detection<br />

time interval.<br />

Set the time interval for detecting loop burnouts.<br />

To disable the LBA function, set 0.<br />

Setting range Unit Default<br />

0 to 9999 Second 0<br />

■ Related Parameters<br />

Alarm 1 type (initial setting level): Page 231<br />

PID* LBA detection time (PID setting level): Page 219<br />

LBA level: Page 259, LBA band: Page 260 (advanced function setting level)<br />

This parameter sets the LBA level.<br />

If the deviation between the SP and PV exceeds the LBA level, a loop<br />

burnout is detected.<br />

Note For ON/OFF control, the LBA Detection Time parameter (advanced<br />

function setting level) must not be set to 0. For 2-PID control, the<br />

LBA Detection Time parameter must not be set to 0 for any of PID<br />

sets 1 to 8.<br />

Note Set “None” as the unit for <strong>Controllers</strong> with Analog Inputs.<br />

Alarm 1 must be assigned.<br />

The alarm type must be set to 12<br />

(LBA).<br />

ON/OFF control must be used.<br />

Alarm 1 must be assigned.<br />

The alarm type must be set to 12 (LBA).<br />

The LBA detection time must not be 0.<br />

(See note.)<br />

Models Setting range Unit Default<br />

Temperature input 0.1 to 3240.0 °C or °F 8.0<br />

Analog Input 0.01 to 99.99 %FS 10.00<br />

■ Related Parameters<br />

Process value/Set point (operation level): Page 177<br />

Alarm 1 type (initial setting level): Page 231<br />

PID * LBA detection time (PID setting level): Page 219<br />

LBA detection time, LBA band: Page 219 (advanced function setting level)<br />