Protect Level Section 5-2<br />

pmov Move to Protect Level<br />

Function<br />

See<br />

172<br />

The password to move to the protect level is entered for this parameter.<br />

The password to move to the protect level (i.e., the password set for the<br />

Password to Move to Protect Level parameter) is entered for this parameter.<br />

The Operation/Adjustment Protect parameter will be displayed if the correct<br />

password is entered.<br />

■ Related Parameters<br />

Password to move to protect level (protect level): Page 174<br />

oapt Operation/Adjustment Protect<br />

icpt Initial Setting/Communications Protect<br />

Function<br />

Setting<br />

The Password to Move to Protect<br />

Level password must not be set to 0.<br />

These parameters specify the range of parameters to be protected. Shaded<br />

settings are the defaults.<br />

■ Operation/Adjustment Protect<br />

The following table shows the relationship between set values and the range<br />

of protection.<br />

Level Set value<br />

0 1 2 3<br />

Operation PV Can be displayed Can be displayed Can be displayed Can be displayed<br />

Level PV/SP Can be displayed Can be displayed Can be displayed Can be displayed<br />

and changed and changed and changed<br />

Others Can be displayed Can be displayed Cannot be dis- Cannot be dis-<br />

and changed and changed played and moving played and moving<br />

to other levels is to other levels is<br />

not possible not possible<br />

Adjustment Level Can be displayed Cannot be dis- Cannot be dis- Cannot be dis-<br />

and changed played and moving played and moving played and moving<br />

to other levels is to other levels is to other levels is<br />

not possible not possible not possible<br />

Parameters are not protected when the set value is set to 0.<br />

■ Initial Setting/Communications Protect<br />

This protect level restricts movement to the initial setting level, communications<br />

setting level, and advanced function setting level.<br />

Set<br />

value<br />

Initial setting level Communications<br />

setting level<br />

Advanced function<br />

setting level<br />

0 Possible to reach Possible to reach Possible to reach<br />

1 Possible to reach Possible to reach Not possible to reach<br />

2 Not possible to reach Not possible to reach Not possible to reach