Initial Setting Level Section 5-9<br />

tr-h Transfer Output Upper Limit A transfer output or linear voltage<br />

output must be supported.<br />

tr-l Transfer Output Lower Limit<br />

Function<br />

Setting<br />

See<br />

236<br />

Transfer output<br />

type<br />

This parameter sets the upper and lower limit values of transfer outputs.<br />

Set point (See<br />

note 1.)<br />

Set point during<br />

SP ramp<br />

SP lower limit to SP upper limit<br />

PV Temperature Input setting range lower limit<br />

to input setting range upper<br />

limit<br />

Analog Analog scaling lower limit to<br />

analog scaling upper limit<br />

MV monitor<br />

(heating) (See<br />

note 2.)<br />

MV monitor<br />

(cooling) (See<br />

note 3.)<br />

Valve opening<br />

(See note 4.)<br />

Note (1) If the set point is selected, the remote SP will be output as long as the<br />

Remote SP Mode is selected in the SP Mode parameter.<br />

(2) This setting will be ignored for position-proportional model.<br />

(3) This setting will be ignored for standard control or position-proportional<br />

control.<br />

(4) This parameter will be displayed only when the is a potentiometer input<br />

for a position-proportional model.<br />

■ Related Parameter<br />

Transfer output type (initial setting level): Page 235<br />

The Transfer Output Type parameter<br />

must not be set to OFF.<br />

Setting range Default Unit<br />

Transfer<br />

output lower<br />

limit<br />

Transfer<br />

output upper<br />

limit<br />

SP lower limit to SP upper limit SP lower limit SP upper limit EU<br />

Input setting<br />

range lower<br />

limit<br />

Scaling lower<br />

limit<br />

Input setting<br />

range upper<br />

limit<br />

Scaling upper<br />

limit<br />

Standard −5.0 to 105.0 0.0 100.0 %<br />

Heating/<br />

cooling<br />

0.0 to 105.0<br />

0.0 to 105.0<br />

Position-proportional<br />

−10.0 to 110.0<br />

o1-t Linear Current Output<br />

The E5CN-H must be used, and the<br />

control output must be a current output.<br />

This parameter selects the output type for linear current outputs.<br />

When control output 1 or control output 2 is a current output, select either<br />

4 to 20 mA or 0 to 20 mA as the output type.