Adjustment Level Section 5-4<br />

See<br />

■ Related Parameters<br />

lcr1 Leakage Current 1 Monitor<br />

Function<br />

Monitor<br />

See<br />

hs1 HS Alarm 1<br />

Function<br />

Setting<br />

Heater current 2 value monitor (adjustment level): Page 182<br />

Heater overcurrent use, Heater overcurrent latch, Heater overcurrent hysteresis<br />

(advanced function setting level): Page 272, 273<br />

This parameter measures the heater current from the CT input used for<br />

detecting SSR short-circuits.<br />

This parameter measures and displays the heater current when the heater is<br />

OFF.<br />

HS alarms are not detected if the control output (heating) OFF time is<br />

100 ms or less.<br />

Monitor range Unit<br />

0.0 to 55.0 A<br />

ffff is displayed when 55.0 A is exceeded.<br />

If an HS alarm 1 alarm is output, the HA indicator will light and the No. 1<br />

display for the leakage current 1 monitor will flash.<br />

■ Related Parameters<br />

HS alarm 1, HS alarm 2 (adjustment level): Page 197<br />

HS alarm use (advanced function setting level): Page 257<br />

Error displays lcr1: Page 306<br />

Heater burnout, HS alarms, and<br />

heater overcurrent detection must be<br />

supported.<br />

Alarm 1 must be assigned.<br />

The HS Alarm parameter must be<br />

set to ON.<br />

Heater burnout, HS alarms, and<br />

heater overcurrent detection must be<br />

supported.<br />

Alarm 1 must be assigned.<br />

The HS Alarm parameter must be<br />

set to ON.<br />

This parameter sets the current for the HS alarm to be output.<br />

An HS alarm is output when the leakage current value exceeds the setting<br />

of this parameter.<br />

When the set value is 50.0, the HS alarm output is turned OFF. When the<br />

set value is 0.0, the HS alarm output is turned ON.<br />

Setting range Unit Default<br />

0.0 to 50.0 A 50.0<br />

197