Using Event Inputs Section 4-5<br />

4-5-2 Operation Commands Other than Bank Selection<br />

Executing Run/Stop<br />

Control<br />

Switching between<br />

Auto and <strong>Manual</strong><br />

Control<br />

98<br />

The following table shows the functions assigned when an Event Input<br />

Assignment (1 to 4) is displayed.<br />

Setting Function<br />

none None<br />

stop RUN/STOP<br />

manu Auto/<strong>Manual</strong><br />

prst Program Start (See note 1.)<br />

drs Invert Direct/Reverse Operation<br />

rsp SP Mode Switch (See note 2.)<br />

at-2 100% AT Execute/Cancel<br />

at-1 40% AT Execute/Cancel (See note 3.)<br />

wtpt Setting Change Enable/Disable<br />

cmwt Communications Write Enable/Disable (See note 4.)<br />

lat Alarm Latch Cancel<br />

Note (1) PRST (Program Start) can be set even when the Program Pattern parameter<br />

is set to OFF, but the function will be disabled.<br />

(2) This function can be selected only with models that support remote SP.<br />

(3) This function can be set for heating/cooling control, but the function will<br />

be disabled.<br />

(4) This function can be selected only with models that support communications.<br />

Also, when a work bit is selected as event input data, Communications<br />

Write Enable/Disable parameter cannot be selected.<br />

When any of the following functions is set for an Event Input Assignment<br />

parameter, the same function cannot be set for another Event Input Assignment<br />

parameter: STOP (RUN/STOP), MANU (Auto/<strong>Manual</strong> Switch), PRST<br />

(Program Start), DRS (Direct/Reverse Operation), RSP (SP Mode Switch),<br />

AT-2 (100% AT Execute/Cancel), AT-1 (40% AT Execute/Cancel), WTPT (Setting<br />

Change Enable/Disable), CMWT (Communications Write Enable/Disable),<br />

or LAT (Alarm Latch Cancel).<br />

Turn event inputs ON and OFF while the power is being supplied. Event input<br />

ON/OFF changes are detected for inputs of 50 ms or longer. (However, inputs<br />

of 250 ms or longer is determined using logic operation.)<br />

The functions are described in detail below. Event inputs 1 and 2 are taken as<br />

examples. When using event inputs 3 and 4, substitute event input 3 for event<br />

input 1 and event input 4 for event input 2.<br />

When the Event Input Assignment 1 or Event Input Assignment 2 parameter<br />

is set to STOP (RUN/STOP), control is started when event input 1 or 2 turns<br />

OFF. Control is stopped when the input turns ON. Alarm outputs, however, will<br />

be according to the process value.<br />

The STOP indicator will light while control is stopped.<br />

Setting Input contact Status<br />

Event input 1 or 2 ON STOP<br />

Event input 1 or 2 OFF RUN<br />

When the Event Input Assignment 1 or Event Input Assignment 2 parameter<br />

is set to MANU (auto/manual), manual control will start when event input 1 or<br />

2 turns ON. Auto control will start when the input turns OFF.