Adjustment Level Section 5-4<br />

of-r <strong>Manual</strong> Reset Value<br />

Function<br />

Setting<br />

See<br />

202<br />

This parameter sets the required manipulated variable to remove offset<br />

during stabilization of P or PD control.<br />

Setting range Unit Default<br />

0.0 to 100.0 % 50.0<br />

■ Related Parameters<br />

PID * integral time (PID setting level): Page 217<br />

PID ON/OFF (initial setting level): Page 228<br />

The control must be standard control<br />

and 2-PID control.<br />

The Integral Time parameter for PID<br />

sets 1 to 8 must be set to 0.<br />

hys Hysteresis (Heating) The control must be ON/OFF control.<br />

For the Hysteresis (Cooling) parame-<br />

chys Hysteresis (Cooling)<br />

Function<br />

Setting<br />

See<br />

Parameter<br />

name<br />

Hysteresis<br />

(Heating)<br />

Hysteresis<br />

(Cooling)<br />

ter, the control must be heating/cooling<br />

control.<br />

This parameter sets the hysteresis for ensuring stable operation at the ON/<br />

OFF switching point.<br />

For standard control, use the Hysteresis (Heating) parameter. The Hysteresis<br />

(Cooling) parameter cannot be used.<br />

For heating/cooling control, the hysteresis can be set independently for<br />

heating/cooling. The Hysteresis (Heating) parameter is used for the heating<br />

side, and the Hysteresis (Cooling) parameter is used for the cooling<br />

side.<br />

Model Setting range Unit Default<br />

Temperature input 0.1 to 3240.00 °C or °F 1.0<br />

Analog Input 0.01 to 99.99 %FS 0.10<br />

Temperature input 0.1 to 3240.00 °C or °F 1.0<br />

Analog Input 0.01 o 99.99 %FS 0.10<br />

■ Related Parameters<br />

PID ON/OFF, Standard or heating/cooling (initial setting level): Page 228