Wiring Terminals Section 2-2<br />

Take countermeasures such as installing a surge absorber. As an additional<br />

safety measure, provide error detection in the control loop. (Use the<br />

Loop Burnout Alarm (LBA) and HS alarm that are provided for the E5@N-<br />

H.)<br />

Varistor<br />

SSR output<br />

Select a surge absorber that satisfies the following conditions.<br />

Voltage used Varistor voltage Surge resistance<br />

100 to 120 VAC 240 to 270 V 1,000 A min.<br />

200 to 240 VAC 440 to 470 V<br />

Control Output 2 Outputs are sent from terminals 11, 12, 14, and 15 with the E5CN-H, and<br />

from pins 5 and 6 with the <strong>E5AN</strong>/EN-H. The following diagrams show the<br />

available outputs and their internal equalizing circuits.<br />

Relay<br />

The following table shows the specifications for each output type.<br />

E5CN-H<br />

3<br />

4<br />

<strong>E5AN</strong>/EN-H<br />

Varistor<br />

+v<br />

+v<br />

+<br />

11<br />

L or<br />

+<br />

14<br />

L<br />

GND 12<br />

−<br />

GND 15<br />

−<br />

Voltage (for driving SSR) Voltage (for driving SSR)<br />

5<br />

6<br />

E5CN-H<br />

SSR<br />

5<br />

6<br />

+v<br />

+<br />

5<br />

L<br />

GND 6<br />

−<br />

E53-Q4 (PNP)<br />

E53-QN (PNP)<br />

Load<br />

~<br />

+v<br />

5<br />

6<br />

+<br />

L<br />

−<br />

V<br />

+<br />

5<br />

L<br />

GND<br />

6<br />

−<br />

E53-Q3 (NPN) E53-V34N<br />

E53-V35N<br />

<strong>E5AN</strong>/EN-H<br />

Output type Specifications<br />

Voltage (for driving<br />

SSR)<br />

+<br />

5<br />

mA L<br />

6<br />

−<br />

E53-C3N<br />

E53-C3DN<br />

PNP type, 12 VDC ±15%, 21 mA (with short-circuit protection)<br />

Output type Specifications<br />

SSR 75 to 250 VAC 1 A (See note.)<br />

Relay (Position- 250 VAC 1 A (including inrush current)<br />

proportionalmodels) Note The SSR output (control output 1 or control output 2) ratings are as<br />

follows:<br />

Rated load voltage: 75 to 250 VAC<br />

Rated load current: 1 A (resistance load)<br />

Use the load current within the derating curve.<br />