Setting Output Specifications Section 3-5<br />

For example, when the process value (PV) is lower than the set point (SP)<br />

in a heating control system, the manipulated variable increases according<br />

to the difference between the PV and SP. Accordingly, reverse operation is<br />

used in a heating control system. Direct operation is used in a cooling control<br />

system, in which the operation is the opposite of a heating control system.<br />

Direct/reverse operation is set in the Direct/Reverse Operation parameter<br />

in the initial setting level. The default is or-r (reverse operation).<br />

Operating Procedure In this example, the input type, temperature unit, direct/reverse operation, and<br />

control period (heat) parameters are checked.<br />

Input type = s (K thermocouple)<br />

Temperature unit = c (°C)<br />

Direct/reverse operation = or-r (reverse operation)<br />

Control period (heat) = 20 (seconds)<br />

Operation Level 1. Press the O Key for at least three seconds to move from the operation<br />

level to the initial setting level.<br />

C<br />

30.0<br />

0.0<br />

Initial Setting Level 2. The input type is displayed. When the input type is being set for the first<br />

Input Type<br />

time, s (K thermocouple) is set. To select a different sensor, press the U<br />

or D Key.<br />

in-t 5<br />

d-u c<br />

cp 20<br />

orev<br />

or-r<br />

Temperature<br />

Unit<br />

Control Period<br />

(Heating)<br />

Direct/Reverse<br />

Operation<br />

3-5-3 Assigned Output Functions<br />

3. Select the Temperature Unit parameter by pressing the M Key. The default<br />

is c (°C). To select f (°F), press the U Key.<br />

4. Select the Control Period (Heating) parameter by pressing the M Key.<br />

The default is 20.<br />

5. Select the Direct/Reverse Operation parameter by pressing the M Key.<br />

The default is or-r (reverse operation). To select or-d (direct operation),<br />

press the U Key.<br />

Operation Level 6. To return to the operation level, press the O Key for at least one second.<br />

C<br />

30.0<br />

0.0<br />

PV/SP<br />

Function assignments can be changed by changing the settings for control<br />

and auxiliary output assignments.<br />

The default function assignments for each output are shown below.<br />

Parameter name Symbol Initial status<br />

Control Output 1 Assignment out1 Control output (heating)<br />

Control Output 2 Assignment out2 Not assigned.<br />

Auxiliary Output 1 Assignment sub1 Alarm 1<br />

53