Determining PID Constants (AT, ST, <strong>Manual</strong> Setup) Section 3-8<br />

3-8-2 ST (Self-tuning)<br />

62<br />

at<br />

off<br />

3. off will be displayed when AT ends.<br />

Operation Level 4. To return to the operation level, press the O Key.<br />

C<br />

25.0<br />

0.0<br />

st<br />

PV<br />

ST (self-tuning) is a function that finds PID constants by using step response<br />

tuning (SRT) when <strong>Digital</strong> Controller operation begins or when the set point is<br />

changed.<br />

Once the PID constants have been calculated, ST is not executed when the<br />

next control operation is started as long as the set point remains unchanged.<br />

ST (self-tuning) is enabled when the ST parameter is set to ON in the initial<br />

setting level.<br />

When the ST function is in operation, be sure to turn the power supply of the<br />

load connected to the control output ON simultaneously with or before starting<br />

Controller operation.<br />

When executing self-tuning, turn ON power for the load (e.g., heater) at the<br />

same time as or before supplying power to the <strong>Digital</strong> Controller. If power is<br />

turned ON for the <strong>Digital</strong> Controller before turning ON power for the load, selftuning<br />

will not be performed properly and optimum control will not be<br />

achieved. ST can be set for standard models only.<br />

Operating Procedure This procedure executes self-tuning (ST).<br />

Initial Setting Level 1. Press the O Key for at least three seconds to move from the operation<br />

Input Type<br />

level to the initial setting level.<br />

in-t 5<br />

st on<br />

ST<br />

2. Select the ST parameter by pressing the M Key.<br />

3. Press the U Key to select on. ON is the default.<br />

Operation Level 4. To return to the operation level, press the O Key for at least one second.<br />

The temperature display flashes during self-tuning (ST) execution.<br />

C<br />

PV<br />

25.0<br />

100.0<br />

Note PID Constants<br />

When control characteristics are already known, PID constants can be set<br />

directly to adjust control. PID constants are set in the Proportional Band (P),<br />

Integral Time (I), and Derivative Time (D) parameters, according to the Display<br />

PID Selection parameter setting in the PID setting level. Changing the<br />

Proportional Band (P), Integral Time (I), or Derivative Time (D) parameter settings<br />

in the adjustment level changes the settings in these parameters in the<br />

current PID set.