Advanced Function Setting Level Section 5-10<br />

See<br />

248<br />

■ Related Parameters<br />

PID ON/OFF: Page 228, ST: Page 228 (initial setting level)<br />

at-g AT Calculated Gain Control must be set to 2-PID control.<br />

at-h AT Hysteresis<br />

lcma Limit Cycle MV Amplitude<br />

Function<br />

Setting<br />

See<br />

Normally use the default values for these parameters.<br />

The AT Calculated Gain parameter sets the gain for when PID values are<br />

calculated using AT. When emphasizing response, decrease the set<br />

value. When emphasizing stability, increase the set value.<br />

The AT Hysteresis parameter sets the hysteresis for limit cycle operation<br />

during autotuning when switching ON and OFF.<br />

The Limit Cycle MV Amplitude parameter sets the MV amplitude for limit<br />

cycle operation during autotuning.<br />

Parameter name Setting range Unit Default<br />

AT Calculated Gain 0.1 to 10.0 --- 1.0<br />

AT Hysteresis Temperature<br />

input: 0.1 to<br />

3,240.0<br />

°C or °F 0.8 (See note 1.)<br />

Analog input:<br />

0.01 to 9.99<br />

%FS 0.20<br />

Limit Cycle MV<br />

Amplitude (See note<br />

2.)<br />

5.0 to 50.0 % 20.0<br />

Note (1) When the temperature unit is °F, the default is 1.4.<br />

(2) With standard models, this is displayed during standard control. With position-proportional<br />

models, this is displayed during close control (when<br />

there is a potentiometer input).<br />

■ Related Parameters<br />

AT execute/cancel (adjustment level): Page 192