Using the Simple Program Function Section 4-16<br />

SP Mode<br />

STRT and RSET can be executed for the simple program without regard<br />

to the SP mode. SP mode changes are enabled while the simple<br />

program is being executed. Timing will continue in the SP mode after<br />

the change.<br />

SP mode Description<br />

LSP Timing is performed according to the SP of the bank being<br />

executed.<br />

RSP Timing is performed according to the remote SP.<br />

RSP Input Errors<br />

Timing will be continued even if an RSP input error occurs while the<br />

simple program is being executed.<br />

Note Timing will be performed according to the PV and remote SP at the<br />

time of the RSP error.<br />

Switching RUN and STOP<br />

Timing will continue if RUN and STOP are switched while the simple<br />

program is being executed.<br />

Changing Banks<br />

If the bank is changed while the simple program is being executed, the<br />

time up to that point will be cleared and timing will start for the new<br />

bank's set value.<br />

Operating Procedure Perform the following procedure to use the simple program function.<br />

Program pattern: STOP<br />

Valid program bank: 1<br />

Bank 0 set point: 150°C, Soak time: 5 min, Wait band: 3°C<br />

Bank 0 set point: 200°C, Soak time: 10 min, Wait band: 5°C<br />

SP0=150.0<br />

PV<br />

RSET → STRT<br />

Wait band = 3<br />

Bank 0<br />

SP0=200.0<br />

Wait band = 5<br />

Bank 1<br />

End display<br />

End output<br />

Soak time = 5 min Soak time = 10 min<br />

STOP<br />

Operation Level 1. Press the O Key for at least three seconds to move from the operation<br />

C<br />

PV/SP<br />

level to the initial setting level.<br />

25.0<br />

100.0<br />

Initial Setting Level 2. Select the Program Pattern parameter by pressing the M Key.<br />

in-t 5<br />

Input Type<br />

139