Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10<br />

80<br />

■ HS Alarm Settings<br />

Operation Level 5. Press the O Key for at least one second to move from the advanced<br />

C<br />

25.0<br />

100.0<br />

3-10-7 Settings: Heater Overcurrent Alarm<br />

function setting level to the initial setting level. Press the O key again for<br />

at least one second to move to the operation level.<br />

Adjustment Level 6. Press the O Key for less than one second to move from the operation<br />

Adjustment Level<br />

Display<br />

level to the adjustment level.<br />

l.adj<br />

lcr1<br />

0.0<br />

hs1<br />

50.0<br />

hs1<br />

2.5<br />

PV/SP<br />

Leakage Current<br />

1 Monitor<br />

HS Alarm 1<br />

7. Select the Leakage Current 1 Monitor parameter by pressing the M Key.<br />

Check the current value. Next, set the HS Alarm 1 parameter.<br />

8. Select the HS Alarm 1 parameter by pressing the M Key. Refer to Calculating<br />

Detection Current Values on page 73 when setting the values.<br />

9. For this example, set 2.5. To return to the operation level, press the O<br />

Key for less than one second.<br />

To activate heater overcurrent alarm, set the Heater Overcurrent Use parameter<br />

to ON in the advanced function setting level and set the Heater Overcurrent<br />

Detection 1 and Heater Overcurrent Detection 2 parameters in the<br />

adjustment level.<br />

Operating Procedure This procedure sets the Heater Overcurrent Detection 1 parameter to 20.0.<br />

■ Moving to the Advanced Function Setting Level<br />

The default setting for the Heater Overcurrent Use parameter is ON, so set<br />

the Heater Overcurrent Detection 1 parameter.<br />

Operation Level 1. Move to the advanced function setting level.<br />

C<br />

PV/SP<br />

25.0<br />

100.0<br />

Press the O Key for at least three seconds to move from the operation<br />

level to the initial setting level.<br />

Initial Setting Level 2. Press the M Key to select the Move to Advanced Function Setting Level<br />

Input Type<br />

parameter. (For details on moving between levels, refer to 4-8.)<br />

in-t 5<br />

Initial Setting Level 3. Press the D Key to enter the password (−169), and move from the initial<br />

setting level to the advanced function setting level.<br />

amov<br />

-169