Using the Transfer Output Section 4-14<br />

Advanced Function Setting Level 4. Press the D Key to enter the password (−169), and move from the initial<br />

Parameter<br />

Initialization<br />

setting level to the advanced function setting level.<br />

4-14 Using the Transfer Output<br />

4-14-1 Transfer Output Function<br />

124<br />

init<br />

off<br />

Advanced Function Setting Level 5. Select the Auto/<strong>Manual</strong> Select Addition parameter by pressing the M<br />

Auto/<strong>Manual</strong><br />

Select Addition<br />

Key.<br />

6. Use the U Key to set the parameter to ON.<br />

(The default is ON.)<br />

7. Press the M Key to select the PF Setting parameter and confirm that it is<br />

set to “A-M.” (“A-M” is the default setting.)<br />

Initial Setting Level 8. Press the O Key for at least one second to move from the advanced<br />

Input Type<br />

function setting level to the initial setting level.<br />

9. Press the O Key for at least one second to move from the initial setting<br />

level to the operation level.<br />

<strong>Manual</strong> Control Level 10. Press the PF Key for at least one second to move from the operation level<br />

C<br />

C<br />

amad<br />

on<br />

amad on<br />

pf<br />

a-m<br />

in-t 5<br />

PV/MV<br />

25.0<br />

0.0<br />

25.0<br />

50.0<br />

to the manual control level.<br />

11. Press the U or D Key to set the manual MV. (In this example, the MV is<br />

set to 50.0%.)<br />

Note The manual MV setting must be saved (see page 14), but values<br />

changed with key operations are reflected in the control output<br />

immediately.<br />

Operation Level 12. Press the PF Key to move from the manual control level to the operation<br />

C<br />

alm<br />

level.<br />

25.0<br />

100.0<br />

▲<br />

▲<br />

The transfer output function can be used by <strong>Controllers</strong> that support a<br />

transfer output (<strong>E5AN</strong>/EN-H@F). For <strong>Controllers</strong> that do not have a transfer<br />

output, a control output can be used as a simple transfer output if the<br />

control output is a current output or a linear voltage output.<br />

To use a transfer output, change the setting for the Transfer Type parameter<br />

to anything other than OFF. (This will enable the Transfer Output Upper<br />

Limit and Transfer Output Lower Limit parameters.)