Calibrating the Transfer Output Section 6-6<br />

Input type 27 or 28:<br />

Input type 29:<br />

6-6 Calibrating the Transfer Output<br />

292<br />

1v-1<br />

5ac0<br />

2v-1<br />

4ad9<br />

str no<br />

Advanced Function<br />

Setting Level<br />

M<br />

adj<br />

30<br />

M<br />

Main Input<br />

Calibration<br />

M<br />

Transfer Output<br />

Calibration<br />

M<br />

Input calibration<br />

display<br />

6. When the M Key is pressed, the status changes as shown to the left.<br />

Set the STV to 1 V.<br />

Allow the count value on the No. 2 display to fully stabilize, then press the<br />

D Key to temporarily register the calibration settings.<br />

If this count value is outside of the specified range, the No. 2 display will<br />

flash and the count value will not be temporarily registered.<br />

7. When the M Key is pressed, the status changes as shown to the left.<br />

The data to be temporarily registered is not displayed if it is not complete.<br />

Press the U Key. The No. 2 display changes to yes. Release the key and<br />

wait two seconds or press the M Key. This stores the temporarily registered<br />

calibration data to EEPROM.<br />

To cancel the saving of temporarily registered calibration data to EE-<br />

PROM, press the M Key (while no is displayed in the No. 2 display) without<br />

pressing the U Key.<br />

8. The calibration mode is ended by turning the power OFF.<br />

For <strong>Controllers</strong> that have a transfer output (<strong>E5AN</strong>/EN-H@@F), transfer<br />

output calibration continues to be performed. For details on the settings,<br />

refer to 6-6 Calibrating the Transfer Output on page 292.<br />

Note: This is displayed only for<br />

<strong>Controllers</strong> that have a<br />

transfer output (<strong>E5AN</strong>/EN-<br />

H@@F).<br />

Use the following procedure for calibration.<br />

1. Connect the DMM to the transfer output terminal.<br />

<strong>E5AN</strong>/EN-H<br />

1<br />

Input power supply<br />

2<br />

27 +<br />

DMM<br />

28 −<br />

For <strong>Controllers</strong> that have a transfer output (E5@N-H@@F),<br />

the Transfer Output Calibration Screen will be displayed<br />

after input calibration has been completed.<br />

E5CN-H<br />

Input power supply<br />

9<br />

10<br />

14 +<br />

DMM<br />

15 −