Initial Setting Examples Section 3-1<br />

Example 2<br />

Input type: 9 (T thermocouple,<br />

−200.0°C to 400.0°C)<br />

Control method: PID control<br />

PID constants found using<br />

auto-tuning (AT).<br />

Alarm type: 2 upper limit<br />

Alarm value 1: 30°C<br />

Set point: 150°C<br />

Setup Procedure<br />

Initial Setting<br />

Level<br />

Adjustment<br />

Level<br />

(When PID<br />

control is<br />

selected)<br />

Operation<br />

Level<br />

Power ON<br />

Set input<br />

specifications<br />

Set control<br />

specifications<br />

Set alarm type<br />

AT execution<br />

Set alarm value<br />

Start operation<br />

PV/SP<br />

after AT is<br />

stopped<br />

C<br />

25.0<br />

150.0<br />

C<br />

26.0<br />

150.0<br />

The set point<br />

flashes during<br />

auto-tuning (AT)<br />

execution.<br />

After AT is<br />

stopped<br />

at<br />

off<br />

During AT<br />

execution<br />

at<br />

at-1<br />

Operation Level<br />

Initial Setting<br />

Level<br />

Use the U and<br />

D keys to<br />

select the input<br />

type.<br />

Power ON<br />

C<br />

C<br />

C<br />

25.0<br />

0.0<br />

in-t<br />

9<br />

M<br />

cntl<br />

pid<br />

Press the O key<br />

(for less than 1 s).<br />

To execute<br />

100%AT: at-2<br />

To execute at 40%AT: at-1<br />

off To cancel<br />

AT: off<br />

Press the O key<br />

(for less than 1 s).<br />

25.0<br />

150.0<br />

M<br />

r-s<br />

run<br />

M<br />

al-1<br />

30.0<br />

M<br />

PV/SP<br />

Press the O key for<br />

at least 3 s.<br />

Control stops.<br />

Input Type:<br />

Use the U and<br />

D keys to select<br />

PID control.<br />

ON/OFF<br />

control:<br />

PID<br />

onof<br />

pid<br />

M control:<br />

Use the U and<br />

D keys to set ST<br />

to OFF.<br />

st<br />

off<br />

M<br />

To execute on<br />

ST:<br />

To cancel off<br />

ST:<br />

When ON, self-tuning<br />

operates.<br />

Check the<br />

control period.<br />

Control Period<br />

cp (Heat) 20<br />

20 (Unit: Seconds)<br />

M<br />

It is recommended that 20 seconds<br />

be set for a relay output and 2<br />

seconds for an SSR voltage output.<br />

Check the<br />

alarm type. alt1 Alarm 1 Type:<br />

2<br />

M<br />

2<br />

Operation Level<br />

Press the O key for<br />

at least 1 s.<br />

Control starts.<br />

Use the U and<br />

D keys to set<br />

the SP to 150°C.<br />

C<br />

25.0 PV/SP:<br />

150.0<br />

150.0<br />

Adjustment<br />

Level<br />

Execute AT.<br />

Operation Level<br />

Confirm that<br />

the set point<br />

is 150°C.<br />

Confirm that<br />

control is<br />

running.<br />

Use the U and<br />

D keys to set<br />

the alarm value<br />

to 30°C.<br />

Start operation.<br />

PV/SP<br />

Running<br />

Stopped<br />

Alarm<br />

Value 1<br />

9<br />

run<br />

stop<br />

30.0<br />

To execute 100% AT (auto-tuning),<br />

select at-2. To execute 40% AT,<br />

select at-1. To cancel AT, select<br />

off: (AT cancel).<br />

47