Using Event Inputs Section 4-5<br />

4-5 Using Event Inputs<br />

4-5-1 Event Input Settings<br />

96<br />

Depending on the Controller, there are either two event inputs (event<br />

inputs 1 and 2 or 3 and 4) or four event inputs (event inputs 1 to 4). The<br />

number of event inputs that can be used varies. (Only the <strong>E5AN</strong>/EN-H<br />

has event inputs 3 and 4.)<br />

Event inputs can be used for Bank Selection, RUN/STOP, Auto/<strong>Manual</strong><br />

Switch, Program Start, Direct/Reverse Operation, SP Mode Switch<br />

(<strong>E5AN</strong>/EN-H only), 100% AT Execute/Cancel, 40% AT Execute/Cancel,<br />

Setting Change Enable/Disable, Communications Write Enable/Disable,<br />

and Alarm Latch Cancel.<br />

Of these, only the number of event inputs (0 to 3) set in the Bank Numbers<br />

Used parameter (initial setting level) are used for the bank selection<br />

function.<br />

Event inputs (1 to 4) that are not used for the bank selection function are<br />

assigned using the Event Input Assignment (1 to 4) parameters (initial<br />

setting level).<br />

Event inputs can be used on the following models:<br />

Two Event Inputs;<br />

E5CN-H@M@-500 with the E53-CN@B@N2 for the E5CN-H<br />

<strong>E5AN</strong>/EN-H@B@M@-500 for the <strong>E5AN</strong>/EN-H<br />

Four Event Inputs;<br />

<strong>E5AN</strong>/EN-H@B@M@-500 with the E53-AKB for the <strong>E5AN</strong>/EN-H<br />

When using event inputs for bank selection, the event input assignment<br />

screen will not be displayed. Whether the set value and event input<br />

assignments 1 to 4 will be displayed or hidden is shown in the tables<br />

below.<br />

Do not connect the contacts from the same switch for more than one<br />

E5@N <strong>Controllers</strong>.<br />

<strong>Controllers</strong> with Event Inputs 1 and 2 (Two Event Inputs)<br />

Event input assignment 1 Event input assignment 2<br />

Bank Numbers Used 0 Displayed (Bank selection not used.)<br />

1 Hidden (Bank, 2 points) Displayed (Event input 2 not<br />

used for bank selection.)<br />

2 Hidden (Bank, 4 points)<br />

<strong>Controllers</strong> with Event Inputs 3 and 4 (Two Event Inputs)<br />

Event input assignment 3 Event input assignment 4<br />

Bank Numbers Used 0 Displayed (Bank selection not used.)<br />

1 Hidden (Bank, 2 points) Displayed (Event input 4 not<br />

used for bank selection.)<br />

2 Hidden (Bank, 4 points)