Performing <strong>Manual</strong> Control Section 4-13<br />

Initial Setting Level 15. Press the O Key for at least one second to move from the advanced<br />

Input Type<br />

function setting level to the initial setting level.<br />

in-t 5<br />

Operation Level 16. Press the O Key for at least one second to move from the initial setting<br />

C<br />

PV/SP<br />

25.0<br />

100.0<br />

level to the operation level.<br />

4-13 Performing <strong>Manual</strong> Control<br />

4-13-1 <strong>Manual</strong> Operation<br />

With standard models, the MV is manipulated directly. With position-proportional<br />

models, the MV is manipulated through the amount of valve<br />

opening or by parameter settings.<br />

The manipulated variable can be set in manual mode if the PV/MV parameter<br />

is displayed in the manual control level. The final MV used in automatic<br />

mode will be used as the initial manual MV when moving from<br />

automatic mode to manual mode. In manual mode, the change value will<br />

be saved immediately and reflected in the actual MV.<br />

<strong>Manual</strong> operation can be used only for PID control.<br />

Standard Models The automatic display return function will not operate in manual mode.<br />

Balanceless-bumpless operation will be performed for the MV when<br />

switching from manual operation to automatic operation. (See note.)<br />

If a power interruption occurs during manual operation, manual operation<br />

will be restarted when power is restored using the same MV as when<br />

power was interrupted.<br />

Switching between automatic and manual operation is possible for a maximum<br />

of one million times.<br />

The overall manual operation is illustrated in the following figure.<br />

Position-proportional<br />

Models<br />

0<br />

<strong>Manual</strong><br />

Automatic<br />

MV (%)<br />

MV switched<br />

Balanceless-bumpless<br />

OFF<br />

Power interrupted<br />

When floating control is used or when the Direct Setting of Position Proportional<br />

MV parameter is set to OFF:<br />

Pressing the U Key turns ON the open output, and pressing the D<br />

Key turns ON the close output.<br />

ON<br />

Time<br />

119