Using the Simple Program Function Section 4-16<br />

134<br />

■ Pattern 2 (CONT)<br />

Control will continue in RUN mode when the program has ended.<br />

Set point n<br />

SP<br />

PV<br />

■ Pattern 3 (LOOP)<br />

Soak time<br />

END display<br />

END output<br />

RUN mode continues.<br />

Bank n (end bank)<br />

Wait band<br />

Wait band<br />

At the end of the program, operation switches to the start bank and continues<br />

in RUN mode.<br />

Set point n<br />

SP<br />

PV<br />

Soak time<br />

Bank n (end bank)<br />

Set point 0<br />

Wait ban<br />

Wait ban<br />

RUN mode continues.<br />

Bank 0 (start bank)<br />

Starting Method Any of the following three methods can be used to start the simple program.<br />

Setting the Program Start parameter to STRT.<br />

Turning ON an event input. (The program start must be assigned to an<br />

event input. See note.)<br />

Starting with an Operation Command using communications. (When the<br />

program start is not assigned to an event input.)<br />

Note When an event input is used to start and reset the simple program, writing is<br />

performed to EEPROM. Be sure to consider the write life (1 million writes) of<br />

the EEPROM in the system design. When the program start is assigned to an<br />

event input, the Program Start parameter will function as a monitor display,<br />

and the RSET/STRT displays can be used to check when the event input has<br />

started or reset the simple program. When this is done, the Program Start<br />

parameter functions as a monitor display only and cannot be changed using<br />

key operations. If the Program Pattern parameter is set to OFF, the event input<br />

assignment setting will be initialized to “None.”