User Calibration Section 6-2<br />

6-2 User Calibration<br />

6-2-1 Calibrating Inputs<br />

When calibration has been performed after purchase, the user calibration<br />

information shown in the following illustration will be displayed when moving to<br />

the calibration level.<br />

.adj 30<br />

6-2-2 Registering Calibration Data<br />

A dot is displayed.<br />

The E5@N-H is correctly calibrated before it is shipped from the factory, and<br />

normally need not be calibrated by the user.<br />

If, however, it must be calibrated by the user, use the parameters for calibrating<br />

temperature input and analog input. <strong>OMRON</strong>, however, cannot ensure the<br />

results of calibration by the user. Also, calibration data is overwritten with the<br />

latest calibration results. The default calibration settings cannot be restored<br />

after user calibration. Perform user calibration with care.<br />

The input type selected in the parameter is used for calibration. The input<br />

types are as follows:<br />

<strong>Controllers</strong> with Thermocouple, Resistance Thermometer, Analog Universal<br />

Inputs<br />

Thermocouple: 19 types<br />

Analog input: 5 types<br />

Platinum resistance thermometer: 6 types<br />

The new calibration data for each item is temporarily registered. It can be officially<br />

registered as calibration data only when all items have been calibrated<br />

to new values. Therefore, be sure to temporarily register all items when you<br />

perform the calibration. When the data is registered, it is also recorded that<br />

user calibration has been performed.<br />

Prepare separate measuring devices and equipment for calibration. For<br />

details on how to handle measuring devices and equipment, refer to the<br />

respective instruction manuals.<br />

6-3 Thermocouple Calibration (Thermocouple/Resistance<br />

Thermometer Input)<br />

Calibrate according to the type of thermocouple: thermocouple 1 group<br />

(input types 5, 7, 11, 12, 15, 19, 20) and thermocouple 2 group (input<br />

types 6, 8, 9, 10, 13, 14, 16, 17, 18, 21, 22, 23).<br />

When calibrating, do not cover the bottom of the Controller. Also, do not<br />

touch input terminals/pins (terminals 4 and 5 on the E5CN-H, and pins 19<br />

and 20 on the <strong>E5AN</strong>/EN-H) or compensating conductors.<br />

285